Annual Maintenance Log Book
Contractor name
Site name
Cylinder unit maintenance record sheet
Warranty number
No.
Mechanical
Turn OFF water supply, drain potable circuit, remove mesh from strainer
1
clean and replace in strainer. *1
Drop the primary/heating system pressure to zero check and if necessary
2
top up the expansion vessel (1 bar). Air valve of expansion vessel is TR-
412.
Check and if necessary top up the concentration of anti-freeze/inhibitor (if
3
used in the system).
4
Open the pressure relief valves. Check for unrestricted discharge to the
tundish and that the valves reseat correctly. Check there are no blockages
5
in the tundish and associated pipework and re-pressurise to 1 bar.
Heat system and check pressure does not rise above 3 bar and no water
6
is released from the safety valves.
7
Release any air from the system.
8
the heat emitter does not rise when running the DHW mode.
Electrical
1
Check condition of cables.
2
3
Check and record the operation voltage.
Controller
1
2
Check operation of motorized valves ensure they reseat correctly.
3
Check battery power of wireless thermostat and replace if necessary.
Outdoor heat pump unit maintenance record sheet
Model number
Mechanical
1
Inspect grill and air inlet for trapped debris/damage.
2
Check condensate drain provision.
3
Check integrity of water pipework and insulation.
4
Check all electrical connections.
* Checks should be carried out once a year.
*1 Be sure to reattach the mesh after washing.
Note:
unit. This is especially important when installing on an existing system.
In addition to annual servicing, it is necessary to replace or inspect some parts after a certain period of system operation. Please see tables below for detailed instruc-
Parts which require regular replacement
Parts
Pressure relief valve (PRV)
Air vent (Auto)
Manometer
GCH15010
Replace every Possible failures
6 years
Water leakage
Engineer name
Site number
Model number
Serial number
Frequency
Notes
-
Frequency
Notes
Frequency
Notes
Serial number
Frequency
Notes
Parts which require regular inspection
Parts
Check every
Water circulation pump 1
50,000 hrs (7 years)
Parts which must NOT be reused when servicing
* O-ring
* Gasket
80
Possible failures
Water circulation pump
failure