Start-up, calibration and operation of the burner

6.1

Notes on safety for the first start-up

The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
tions of the laws in force.
WARNING
6.2

Combustion adjustment

In conformity with EN 267, the installation of the burner on the
boiler, the adjustment and testing must be carried out in compli-
ance with the instruction manual of the boiler, including control of
the CO and CO
concentration in the flue gases, their tempera-
2
ture and the average temperature of the water in the boiler.
The temperature of the combustion air (relative to
the place where the burner is installed) may vary
during the season, it influences the CO
burner. We recommend adjusting the CO
WARNING
upon the temperature of the combustion air at the
time when the burner calibration is carried out in
accordance with what is shown in the following di-
agram.
E.g. with combustion air temperature of 10°C, ad-
just the CO
2
To suit the required boiler output, choose the nozzle, the pump
pressure and the adjustment of the air damper according to the
following table.
The values in Tab. G refer to 12.5% of CO
with a light oil and ambient temperature of 20°C.
Nozzle
GPH
Angle
2.50
60°
3.00
60°
3.50
60°
4.00
60°
4.50
60°
4.50
60°
6.3

Recommended nozzles

The burner complies with the emission requirements of the EN
267 standard. In order to guarantee that emissions do not vary,
recommended and/or alternative nozzles specified by manufac-
turer in the Instruction and warning booklet should be used.
It is advisable to replace nozzles every year dur-
ing regular maintenance operations.
WARNING
Steinen
type S - SS
Danfoss
type S - B
Delavan
type B - W
Monarch type R
Start-up, calibration and operation of the burner
to 12.5%.
at sea level, and
2
Pump
Pressure
bar
12
12
12
12
12
14
WARNING
14.5
14.0
13.5
13.0
of the
2
12.5
based
2
12.0
11.5
0
Burner
Combustion head
output
adjustment
kg/h ± 4%
Set-point
10.0
0
12.0
1
14.0
2.5
16.1
4
18.1
6
19.5
6
CAUTION
19
GB
Check the correct working of the adjustment, com-
mand and safety devices.
5
10
15
20
25
External air temperature (°C)
Air damper
adjustment
Low flame
Set-point
0.2
0.4
0.7
0.9
1.4
1.4
The use of nozzles other than those specified by
manufacturer and inadequate regular mainte-
nance may result into emission limits non-con-
forming to the values set forth by the regulations
in force, and in extremely serious cases, into po-
tential hazards to people and objects.
The manufacturing company shall not be liable for
any such damage arising from non-observance of
the requirements contained in this manual.
D4604
30
35
40
Fig. 18
High flame
Set-point
1.4
2.1
3.0
3.5
4.5
6.0
Tab. G
20136874