Mounting; General Instructions - Vega VEGATRENN 152 Operating Instructions Manual

Double channel separator for 4 ... 20 ma sensors
Hide thumbs Also See for VEGATRENN 152:
Table of Contents

Advertisement

Mounting options
Ambient conditions
VEGATRENN 152 •
4

Mounting

4.1

General instructions

VEGATRENN 152 is designed for carrier rail mounting (top hat rail
35 x 7.5 according to DIN EN 50022/60715). Due to its protection
rating of IP20, the instrument is suitable for mounting in switching
cabinets. It can be mounted horizontally and vertically.
VEGATRENN 152 is a corresponding, intrinsically safe equipment
and must not be installed in hazardous areas of zone 0/1. A safe
operation is only ensured if the operating instructions and EU type
approval certificate are observed. VEGATRENN 152 must not be
opened.
A distance of 50 mm to the intrinsically safe terminals must be en-
sured when mounting.
The instrument is suitable for standard and extended ambient condi-
tions acc. to DIN/EN/IEC/ANSI/ISA/UL/CSA 61010-1.
Make sure that the environmental and ambient conditions specified in
chapter " Technical data" are maintained.
4 Mounting
9