  • Page 1 Operating Instructions Double channel separator for 4 … 20 mA sensors VEGATRENN 152 Document ID: 50783...
  • Page 2: Table Of Contents

    EU conformity ......................... 18 SIL conformity (optional) ....................18 Environment management system ................. 18 10 Supplement ..........................19 10.1 Technical data ........................ 19 10.2 Dimensions ........................21 10.3 Industrial property rights ....................22 10.4 Trademark ........................22 VEGATRENN 152 •...
  • Page 3 Contents Editing status: 2021-01-27 VEGATRENN 152 •...
  • Page 4: About This Document

    Symbols used Document ID This symbol on the front page of this instruction refers to the Docu- ment ID. By entering the Document ID on www.vega.com you will reach the document download. Information, note, tip: This symbol indicates helpful additional infor- mation and tips for successful work.
  • Page 5: For Your Safety

    During work on and with the device, the required personal protective equipment must always be worn. Appropriate use VEGATRENN 152 is an [EEx ia] separator without separate power supply for connection of 4 … 20 mA/HART sensors in two-wire ver- sion.
  • Page 6: Installation And Operation In The Usa And Canada

    Canadian Electrical Code. Safety instructions for Ex areas For applications in explosion-proof areas (Ex), only devices with cor- responding Ex approval may be used. Observe the Ex-specific safety instructions. These are an integral part of the operating instructions and are enclosed with every device with Ex approval. VEGATRENN 152 •...
  • Page 7: Product Description

    Principle of operation Application area VEGATRENN 152 is a double channel [EEx ia] separator for connec- tion of two 4 … 20 mA/HART sensors in two-wire version. A separate power supply is not necessary. As an associated electrical device, it ensures a galvanic separation between sensor circuit and processing circuit and thus between Ex and non-Ex areas.
  • Page 8: Packaging, Transport And Storage

    • Protected against solar radiation • Avoiding mechanical shock and vibration • Storage and transport Storage and transport temperature see chapter " Supplement - temperature Technical data - Ambient conditions" • Relative humidity 20 … 85 % VEGATRENN 152 •...
  • Page 9: Mounting

    Mounting General instructions Mounting options VEGATRENN 152 is designed for carrier rail mounting (top hat rail 35 x 7.5 according to DIN EN 50022/60715). Due to its protection rating of IP20, the instrument is suitable for mounting in switching cabinets. It can be mounted horizontally and vertically.
  • Page 10: Connecting To Power Supply

    VEGATRENN 152. You can find details of the voltage supply in chapter " Technical data". The voltage supply of VEGATRENN 152 is connected with standard Connection cable cable according to the national installation standards. Make sure that the cable used has the required temperature resist- ance and fire safety for max. occurring ambient temperature...
  • Page 11: Connection Procedure

    Digital communication with the PC is then no longer possible. With low impedance processing systems, a resistor of approx. 230 Ω must be looped into the 4 … 20 mA cable. This resistor is already inte- grated in VEGATRENN 152 and can be chosen through the selection of the respective terminals. Information: When using a HART resistor, keep in mind that there is an additional voltage loss. You can find details in chapter " Technical data".
  • Page 12: Wiring Plan

    Processing circuit 2 (4 … 20 mA/HART, passive output with looped HART resistor) Information: The connection terminals can be detached towards the front, if necessary. This can be useful when working in tight spaces or when exchanging an instrument. VEGATRENN 152 •...
  • Page 13: Setup

    To close it, push the cover at bottom and top firmly onto the front cover until you hear the two retaining clips snap in. HART communication No adjustment or configuration of VEGATRENN 152 is necessary. sockets Via the HART communication sockets, parameter adjustment of the connected HART sensors can be carried out without interrupting the measuring circuit. The resistor (230 Ω) required for this purpose is already integrated in VEGATRENN 152 when connecting the termi- VEGATRENN 152 •...
  • Page 14 6 Setup nals 10/12 (channel 1) or 13/15 (channel 2). The adjustment of the connected sensor is carried out via a Windows PC with a parameter adjustment software such as e.g. PACTware and corresponding DTM. VEGATRENN 152 •...
  • Page 15: Diagnostics And Servicing

    Should these measures not be successful, please call in urgent cases 24 hour service hotline the VEGA service hotline under the phone no. +49 1805 858550. The hotline is also available outside normal working hours, seven days a week around the clock.
  • Page 16 Clean the instrument and pack it damage-proof • Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Please contact the agency serving you to get the address for the return shipment. You can find the agency on our home page www.vega.com. VEGATRENN 152 •...
  • Page 17: Dismount

    Disposal The device is made of recyclable materials. For this reason, it should be disposed of by a specialist recycling company. Observe the ap- plicable national regulations. VEGATRENN 152 •...
  • Page 18: Certificates And Approvals

    That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observ- ing the environmental instructions in chapters " Packaging, transport and storage", " Disposal" of these operating instructions. VEGATRENN 152 •...
  • Page 19: Supplement

    Number of sensors 2 x 4 … 20 mA/HART (5 x HART multidrop) Input type Active (sensor power supply by VEGATRENN 152) Terminal voltage 16 … 10 V DC at 4 … 20 mA Terminal voltage with operating voltage > 19 V Ʋ...
  • Page 20 For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded by entering the serial number of your instrument into the search field under www.vega.com as well as in the general download area. VEGATRENN 152 •...
  • Page 21: Dimensions

    10 Supplement 10.2 Dimensions 20 mm 113 mm (0.79") (4.45") OPEN Fig. 2: Dimensions VEGATRENN 152 VEGATRENN 152 •...
  • Page 22: Industrial Property Rights

    Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.