Vega VEGACAL 69 Operating Instructions Manual page 31

Capacitive double rod electrode for level measurement
Hide thumbs Also See for VEGACAL 69:
Table of Contents

Advertisement

Service - Language
Service - HART mode
Copy sensor data
VEGACAL 69 • Two-wire 4 ... 20 mA/HART
6 Set up with the display and adjustment module PLICSCOM
Function
Current output - failure
Special parameters
All special parameters are reset to delivery status.
Peak value indicator
The min. and max. values are reset to the actual value.
The sensor is already set to the ordered national language. In this
menu item you can change the language. The following languages are
available as of software version 3.50:
Deutsch
English
Français
Espanõl
Pycckuu
Italiano
Netherlands
Japanese
Chinese
Language
German
HART offers standard and multidrop mode.
The mode "standard" with the fixed address 0 means outputting the
measured value as a 4 ... 20 mA signal.
In Multidrop mode, up to 15 sensors can be operated on one two-wire
cable. An address between 1 and 15 must be assigned to each sen-
sor.
4)
In this menu item you determine the HART mode and enter the ad-
dress for multidrop.
HART mode
Standard
Address 0
The default setting is standard with address 0.
With this function
Load parameter adjustment data from the sensor into the display
and adjustment module
Write parameter adjustment data from the display and adjustment
module into the sensor
The 4 ... 20 mA signal of the sensor is switched off. The sensor uses a
4)
constant current of 4 mA. The measuring signal is transmitted exclusively as
a digital HART signal.
Reset value
< 3.6 mA
31