Basic adjustment - Sen-
sor TAG
Display - Indicated value
VEGACAL 69 • Two-wire 4 ... 20 mA/HART
6 Set up with the display and adjustment module PLICSCOM
Linearisation curve
Linear
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
Caution:
Note the following if the VEGACAL 69 with corresponding approval is
used as part of an overfill protection system according to WHG (Water
Resources Act):
If a linearisation curve is selected, the measuring signal is no longer
necessarily linear to the filling height. This must be considered by the
user especially when setting the switching point on the limit signal
transmitter.
In this menu item you can enter an unambiguous designation for the
sensor, e.g. the measurement loop name or the tank or product des-
ignation. In digital systems and in the documentation of larger plants,
a singular designation should be entered for exact identification of
individual measuring points.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is finished and you can
now jump to the main menu with the [ESC] key.
In the menu item " Display" you can define how the measured value
should be presented on the display.
The following indication values are available:
Height
Distance
Current
Scaled
Percent
Lin. percent
The selection " scaled" opens the menu items " Display unit" and "
Scaling". In " Display unit" there are the following options:
Height
Ground
Flow
Volume
Without unit
Depending on selection, the different units are in turn available.
In the menu item " Scaling", the requested numerical value with deci-
mal point is entered for 0 % and 100 % of the measured value.
27