PRELImINARY INSTALLATION (continued)
INPUT AND OUTPUT BREAKER SIZE
OUTPUT KVA OUTPUT KVA
CONTINUOUS
110 K(I)
50 kVA

wEIghTS, bTU ANd dImENSIONS

UNIT SIZE IN KVA (I)
110 K(I)
* Stated BTU's / Hr is at 100% rated load, 100% duty cycle. Operational BTU's / Hr is typically at 65% of rated
load.
To reduce the risk of fire, use only on circuits provided with ampere
branch circuit protection as noted in the table above, in
accordance with the National Electric Code, ANSI/NFPA 70.
If unit is provide with no output circuit breaker option, output over-current protection
and a disconnect device (circuit breaker) shall be provided by others.
INPUT
BREAKER SIZE
175A @ 380 V
175A @ 400 V
175A @ 415 V
WEIGHT
OPERATIONAL BTU/
HR TYPICAL
1,254 lbs.
3,410*
568.8 kg.
**** CAUTION ****
OUTPUT BREAKER SIZE
Output #1 - 80 A, 3P for 400/230V
Output #2 - 60 A, 3P for 400/230V
MAXIMUM
BTU/HR
6,820
MAX OUTPUT CURRENT
Output #1 65A Continuous Rating
Output #2 65A Momentary Rating
for 30 seconds @ 4.2%
duty cycle
DIMENSIONS
29" W x 35.875" D x 66.0" H
(73.6 cm. x 91.1 cm. x 167.6 cm.)
7
1402-001