Series 700 A/VS Power Conditioner
110K(i) Power Conditioner with
Voltage Regulation (50 Hz)
Owners Manual
Important safety instructions - save these instructions and review prior to using equipment
Dual Output Power Conditioner
with Voltage Regulation
110K(i) 50 Hz Model Front Access Design
▪ 111711 Rev 5

Advertisement

Table of Contents
loading

Summary of Contents for Infinite Transtector 700 A/VS Series

  • Page 1 Series 700 A/VS Power Conditioner 110K(i) Power Conditioner with Voltage Regulation (50 Hz) Owners Manual Important safety instructions - save these instructions and review prior to using equipment Dual Output Power Conditioner with Voltage Regulation 110K(i) 50 Hz Model Front Access Design ▪...
  • Page 2: Table Of Contents

    110K(i) 50 Hz Power Conditioner | Owners Manual TABLE OF CONTENTS Receiving and Inspecting the Unit General Description Safety Precautions Preliminary Installation Weights, BTU and Dimensions Input Wire Size, Grounding and Output Wiring Installation 10-13 Bypass Switch Start - up Preventive Maintenance Performance Checklist General Troubleshooting...
  • Page 3: Receiving And Inspecting The Unit

    RECEIVING & INSPECTING THE UNIT INSPECTING THE POWER PROCESSOR Upon receipt of the unit, visually inspect for shipping damage. If any damage is found, the Purchaser must contact the Carrier immediately and file a shipping damage claim. NOTE: Be sure to remove the front and side panels, and inspect the inside of the unit for shipping damage. If any internal damage has occurred or any external damage that could affect the operation of the unit, please contact Transtector.
  • Page 4: General Description

    110K(i) 50 Hz Power Conditioner | Owners Manual GENERAL DESCRIPTION The Series 700 A/VS Power Processor is designed to supply reliable, clean regulated power to critical loads. An efficient design with state of the art micro-processor controlled solid state devices provide immunity to all line disturbances.
  • Page 5: Safety Precautions

    SAFETY PRECAUTIONS **** WARNING **** THERE ARE DANGEROUSLY HIGH VOLTAGES PRESENT WITHIN THE ENCLOSURE OF THE POWER SUPPLY SYSTEM. CAUTION MUST BE TAKEN WHEN WORKING WITH THE SYSTEM. IT IS RECOMMENDED THAT ALL WORK BE PERFORMED BY QUALIFIED ELECTRICAL PERSONNEL ONLY. **** CAUTION **** RISK OF ELECTRICAL SHOCK AND HIGH SHORT CIRCUIT CURRENT.
  • Page 6: Preliminary Installation

    110K(i) 50 Hz Power Conditioner | Owners Manual PRELIMINARY INSTALLATION INSTALLATION CONSIDERATIONS Prior to installing the Series 700A/VS, be sure to take into consideration the site you have selected. Power Conditioners produce heat and therefore require ventilation as well as accessibility. Consider these factors. ▪...
  • Page 7: Weights, Btu And Dimensions

    PRELImINARY INSTALLATION (continued) INPUT AND OUTPUT BREAKER SIZE OUTPUT KVA OUTPUT KVA INPUT OUTPUT BREAKER SIZE MAX OUTPUT CURRENT CONTINUOUS BREAKER SIZE 110 K(I) 50 kVA 175A @ 380 V Output #1 - 80 A, 3P for 400/230V Output #1 65A Continuous Rating 175A @ 400 V Output #2 - 60 A, 3P for 400/230V Output #2 65A Momentary Rating...
  • Page 8: Input Wire Size, Grounding And Output Wiring

    110K(i) 50 Hz Power Conditioner | Owners Manual INPUT WIRE SIZE, GROUNDING AND OUTPUT WIRING Refer to the latest edition of The National Electric Code Requirements for over-current protection and wire sizing. A. Conduit should be used for both input and output wiring. B.
  • Page 9 INPUT WIRE SIZE, GROUNDING AND OUTPUT WIRING (continued) The unit is constructed using an isolation transformer and is considered to be a “separately derived system”. It should be grounded in accordance with the NFPA 70 article 250.20 “Alternating-Current Circuits and Systems to be grounded”, article 250.20(d) “Separately derived Systems” and article 250.30 “grounding Separately derived Alternating-Current Systems”.
  • Page 10: Installation

    110K(i) 50 Hz Power Conditioner | Owners Manual INSTALLATION CABINET OUTLINE - FRONT VIEW FRONT VIEW 66.000" 167.64 cm 63.000" 160.02 cm INLET...
  • Page 11 INSTALLATION (continued) CABINET OUTLINE - TOP AND BOTTOM VIEW TOP VIEW NO CLEARANCE REQUIRED IN BACK OF UNIT 29.000 73.66 cm OUTLET 35.875 91.12 cm TOP INPUT/OUTPUT LOCATION 6.895 17.51 cm 3.187 8.09 cm 8.000 3.874 20.32 cm 9.84 cm NO CLEARANCE REQUIRED ON LEFT SIDE OF UNIT OPTIONAL 12"...
  • Page 12 110K(i) 50 Hz Power Conditioner | Owners Manual INSTALLATION (continued) CABINET OUTLINE - RIGHT SIDE VIEW AIR FLOW RIGHT SIDE NO CLEARANCE REQUIRED IN BACK OF UNIT OPTIONAL SIDE OUTPUT TERMINATION ACCESS AREA 8.250 20.96 cm 12.06 cm 4.750 2.812 4.500 11.43 cm 7.14 cm...
  • Page 13 INSTALLATION (continued) INPUT AND OUTPUT CONNECTIONS 1. Input connections are made directly to the unit’s 3 pole main input circuit breaker and input ground lug provided. Note the bottom access wire run route illustrated below. 2. Output connections are made directly to the output breaker(s) and output neutral and ground bus provided.
  • Page 14: Bypass Switch

    110K(i) 50 Hz Power Conditioner | Owners Manual BYPASS SWITCH **** CAUTION **** Prior to switching from one position to another- turn off the AC input breaker. The manual bypass switch is a break before make switch located on the Series 700A/VS. The manual bypass switch is used to bypass all power electronics in case of failure.
  • Page 15: Start Up

    START UP **** WARNING **** THERE ARE DANGEROUSLY HIGH VOLTAGES PRESENT WITHIN THE ENCLOSURE OF THE POWER SUPPLY SYSTEM. CAUTION MUST BE TAKEN WHEN WORKING WITH THE ENCLOSURE. IT IS RECOMMENDED THAT ALL WORK BE PERFORMED BY QUALIFIED ELECTRICAL PERSONNEL ONLY. NOTE: INITIAL START-UP SHOULD BE PERFORMED WITH NO LOAD ON SYSTEM.
  • Page 16: Preventive Maintenance

    110K(i) 50 Hz Power Conditioner | Owners Manual PREVENTIVE MAINTENANCE **** WARNING **** dANgER OF ELECTRICAL ShOCK, TURN OFF ALL POwER SUPPLYINg ThIS EqUIPmENT PRIOR TO MAINTENANCE. To ensure longer component life and trouble-free operation, minor preventive maintenance procedures should be performed at regular intervals, for example once every year. More frequent inspection intervals would be needed for more severe operating conditions and larger number of hours of continuous operation.
  • Page 17: Performance Checklist

    PERFORMANCE CHECKLIST Company______________________________________________________________ Model #____________________________Serial #__________________ Customer Comments or Problems____________________________________ Power Processor Environment Clean and Dust Free Yes_______ No________ Phase Rotation Correct (ABC) Yes_______ No________ Electrically wired properly ie...Conductor Sizing, Breakers, Grounding Verify Input Voltage (See specification tag) Check Tightness of Electrical Connections: ______Input Connections______Output Connections______Heatsink Connections (SCR’s) ______Circuit Board Connections______By-Pass Switch______Fuse Connections ______Fan Connections______Transformer Connections...
  • Page 18: General Troubleshooting

    110K(i) 50 Hz Power Conditioner | Owners Manual GENERAL TROUBLESHOOTING **** WARNING **** THERE ARE DANGEROUSLY HIGH VOLTAGES PRESENT WITHIN THE ENCLOSURE OF THE POWER SUPPLY SYSTEM. CAUTION MUST BE TAKEN WHEN WORKING WITH THE ENCLOSURE. IT IS RECOMMENDED THAT ALL WORK BE PERFORMED BY QUALIFIED ELECTRICAL PERSONNEL ONLY.
  • Page 19: Parts List

    PARTS LIST 380 V INPUT 400 V INPUT 415 V INPUT DESCRIPTION PART # 204382 204382 204382 MAIN TRANSFORMER 104034 104034 104034 MAIN INPUT BREAKER 17694 17694 17694 FILTER CAPACITOR 16777 16777 16777 FILTER RESISTOR 19149 19149 19149 CONTROL FUSE (3A) 110366 110366 110366...
  • Page 20: Warranty

    110K(i) 50 Hz Power Conditioner | Owners Manual WARRANTY WARRANTY VALIDATION WARRANTY VOID UNLESS THIS FORM IS COMPLETE AND RETURNED TO TRANSTECTOR SYSTEMS Transtector Systems, Inc. warrants that the Series 700 A/VS Power Conditioner and its components will remain free from defects in material and workmanship for the period of two (2) years from the date of shipment and agrees to replace F.O.B.
  • Page 21 APPENDIX A RELATIVE DRAWINGS & SCHEMATICS 1402-001...
  • Page 22: Cabinet Layout

    110K(i) 50 Hz Power Conditioner | Owners Manual CABINET LAYOUT...
  • Page 23 CABINET LAYOUT 1402-001...
  • Page 24 110K(i) 50 Hz Power Conditioner | Owners Manual CABINET LAYOUT NO CLEARANCE REQUIRED...
  • Page 25: Seismic Calculations

    SEISMIC CALCULATIONS Coastal California, Zone 4 Z = 0.4 Equipment Anchorage I = 1.5 Uniform Building Code, Table 160 Cp = 0.75 Fp = Z x I x (Cp) x Wp = 0.45 x Wp Cabinet Weight 1254 lbs. Center of Gravity Height 24.375 in.
  • Page 26: Symbol Library

    110K(i) 50 Hz Power Conditioner | Owners Manual SYMBOL LIBRARY This symbol indicates that caution should be taken when performing the process required in this manual. Damage to the unit or personal harm could happen if proper precautions are not taken. Caution This symbol indicates that there is a risk of electrical shock if proper precau- tions are not followed.
  • Page 27: Notes

    NOTES 1402-001...