110K(i) 50 Hz Power Conditioner | Owners Manual
14
BYPASS SWITCH
**** CAUTION ****
Prior to switching from one position to another- turn off the AC input breaker.
The manual bypass switch is a break before make switch located on the Series 700A/VS. The manual
bypass switch is used to bypass all power electronics in case of failure.
NORMAL MODE
With the switch in the normal position, the Series 700A/VS will provide clean and regulated power to the
critical loads. The Series 700A/VS should have the switch in the normal position unless a failure has
occurred.
BYPASS MODE
With the switch in the bypass position, the Series 700A/VS will provide clean power to the critical loads.
In the bypass position, the unit will not regulate the incoming voltage. The Series 700A/VS should be
placed in the bypass position when a failure of the system has occurred. This provides the user with some
protection until a service technician arrives.
REMOTE EMERGENCY POWER OFF (REPO) OPTION
The REPO is operated by a remote push button that when depressed will shunt trip the Series 700A/VS
input breaker and disable the unit. This option may be added to units in the field.
Contact the Customer Support Department if you wish to add this option.