Pressure switches
Check that the air pressure switch and the gas pressure switch
are set correctly.
Gas leaks
Make sure that there are no gas leaks on the pipe between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
Check there are no occlusions or obstructions in the fuel supply
or return lines, in the air suction areas, and in the combustion
product waste pipe.
Carry out an analysis of the combustion flue gases.
Significant differences with respect to the previous measure-
ments indicate the points where most care should be exercised
during maintenance.
If the combustion values measured before starting maintenance
do not comply with applicable legislation or do not indicate effi-
cient combustion, consult the Tab. N on page 31 or contact our
Technical Support Service to implement the necessary adjust-
ments.
Leave the burner working without interruptions for 10 min. and set
rightly all the components stated in this manual. Then carry out a
combustion check verifying:
Percentage of CO
(%);
2
CO content (ppm)
NOx content (ppm)
Ionisation current (µA)
Smoke temperature at the flue
Maintenance
7.2.4

Safety components

The safety components must be replaced at the end of their life
cycle indicated in Tab. O. The specified life cycles do not refer to
the warranty terms indicated in the delivery or payment
conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic
cam) (if present)
Oil valve (solenoid)(if
present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Flexible hoses (if present)
Fan impeller
33
GB
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000 pressurised
cycles
10 years or 500,000 start-ups
Tab. O
20147064