Electrical Diagram - Riello 40 FS5 Installation, Use And Maintenance Instructions

Forced draught gas burner one-stage operation
Table of Contents

Advertisement

5.10.3 Electrical diagram

Key (Fig. 18)
C
Motor capacitor
CN1
Ionisation probe connector
E
Ignition electrode
h1
Hour counter (230V - 0.1A max.)
MV
Fan motor
PA
Air pressure switch
PG
Min. gas pressure switch
RS
Remote reset connection
SB
Lockout light (230V - 0.5A max.)
SM
One-stage damper conn.
SO
Ionisation probe
TB
Burner earth
TL
Limit thermostat
TS
Safety thermostat
T6A
Fuse
V1
Adjustment valve
VS
Safety valve
XP6
6 pin plug/socket
XP7
7 pin/plug socket
 Do not invert the neutral with the phase in the
electrical supply line.
 Check that the electrical supply of the burner
corresponds to that shown on the identifica-
WARNING
tion label and in this manual.
 The section of the conductors must be at
least 1mm
local standards and legislation).
Check the burner stops by opening the thermo-
stats and check it locks out by opening the con-
nector (CN1)(Fig. 18) inserted in the probe's red
wire, located on the outside of the control box.
WARNING
If the cover is still on, remove it and proceed with
the electric wiring following the wiring diagrams.
Use flexible cables in compliance with EN 60 335-
CAUTION
1 standards.
2
. (Unless requested otherwise by
Installation
19
GB
Main switch
Black
White
Blue
D7057
Fig. 18
20147064