Outdoor Air Quality Sensor

(P/N 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO
sensor is designed to monitor carbon
2
dioxide (CO
) levels in the outside ventilation air and
2
interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 53. The outdoor air CO
economizer outside air hood.
COVER REMOVED
Fig. 53 - - Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO
power supply is required for this sensor. A two- - wire cable
is required to wire the dedicated power supply for the
sensor. The two wires should be connected to the power
supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 51. Connect the 4 to 20 mA
terminal to the RTU Open controller at J4- - 5. Connect the
SIG COM terminal to the RTU Open controller at J4- - 6.
OAQ Sensor/RH Sensor
SEN
COM
24 VAC
Fig. 54 - - RTU Open Controller / Outdoor CO
(33ZCSENCO2) Connections
sensor must be located in the
2
SIDE VIEW
C07135
Sensor: A dedicated
2
J4-5
J4-6
C08463
Sensor
2
Space Relative Humidity Sensor or Humidistat —
The Space Relative Humidity Sensor is not used with 549J
units at this time.
Smoke Detector/Fire Shutdown (FSD) —
On 549J units equipped with factory- - installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit's CTB input. The FSD function is initiated via the
smoke detector's Alarm NO contact set. The RTU Open
controller communicates the smoke detector's tripped
status to the BAS building control. See Fig. 44 (Typical
RTU Open controller wiring diagram).
The
Fire
Shutdown
MENU
Config
Inputs
open status of this input when there is no fire alarm.
Connecting Discrete Inputs —
Filter Status: The filter status accessory is a field- - installed
accessory. This accessory detects plugged filters. When
installing this accessory, the unit must be configured for
filter status by setting MENU
8, or 9 to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 43 and Fig. 44 for wire
terminations at J5.
Fan Status: The fan status accessory is a field- - installed
accessory. This accessory detects when the indoor fan is
blowing air. When installing this accessory, the unit must be
configured
for
fan
MENU
Config
Inputs
and normally open (N/O) or normally closed (N/C). Input 8
or 9 is recommended for easy of installation. Refer to Fig.
43 and Fig. 44 for wire terminations at J5.
Remote Occupancy: The remote occupancy accessory is
a field- - installed accessory. This accessory overrides the
unoccupied mode and puts the unit in occupied mode.
When installing this accessory, the unit must be
configured
for
remote
MENU
Config
Inputs
Occupancy and normally open (N/O) or normally closed
(N/C).
Also set MENU
Schedules
on/off. Input 8 or 9 is recommended for ease of
installation. Refer to Fig. 43 and Table 23 for wire
terminations at J5.
Power Exhaust (output): The relay used by the RTU
Open controller board to control power exhaust is a dry
contact which means it does not have 24vac. This 24vac
must be connected to the relay to allow it to operate the
power exhaust relay in the PE accessory. A 24vac source
must be provided to J11- - 2 on the RTU Open controller
board. This can be provided by the unit's transformer from
various sources. The "R" terminal on the unit's central
terminal board (CTB) is a logical source. Refer to Fig. 43
and Fig. 44 for wire terminations at J11.
44
Switch
configuration,
input 5, identifies the normally
Config
Inputs
input 3, 5,
status
by
input 3, 5, 8, or 9 to Fan Status
occupancy
by
input 3, 5, 8, or 9 to Remote
occupancy source to DI
setting
setting