Section 4
Mounting
20
Raising frame
Gasket
Screws
Requirements for installation:
Panel cut-out of 165.5 × 161.5 mm with mounting holes
Depth behind the panel 103 mm
When IP 54 degree of protection (according to IEC 60529) is required for the
front side, a gasket has to be used in the installation.
1.
Mount the raising frame into the panel cut-out with four M4 screws.
C
D
A070589 V5 EN
Figure 10:
Mounting the raising frame
A 173.5 ±0.3 mm 1 Panel
B 165.5 ±1 mm
2 Raising frame
C 161.5 ±1 mm
3 M4 screw
D 133 ±0.3 mm
E ∅ 5.5 mm
2.
Loosen the four M5 fixing screws in the case to fit the case to the raising frame.
3.
Remove the protective film temporarily from the top side of the case.
4.
Mount the case to the raising frame.
A
B
1MRS757452 D
1
2
3
611 series
Installation Manual