ELECTRICAL SPECIFICATIONS
Nominal Range: 200A
Measurement Range: 0.1 to 240A
Transformation Ratio: Voltage output
Output Signal: 1mV/A
Accuracy and Phase Shift*:
Accuracy: 0.5 to 10A: 3.0% Reading ± 0.5mV
10 to 40A: 2.5% Reading ± 0.5mV
40 to 100A: 2.0% Reading ± 0.5mV
100 to 240A: 1.0% Reading ± 0.5mV
2.00"
(51 mm)
MN251
.73"
(18.5 mm)
Tactical
Barrier
(keep hands below
this barrier)
.1.18"
Phase Shift: 0.5 to 10A: Not Specified
10 to 40A: ≤ 5°
40 to 100A: ≤ 3°
100 to 240A: ≤ 2.5°
(*Reference conditions:18°C to 28°C, 20 to 75% RH, external
magnetic field < 40 A/m, 48 to 65 Hz sine wave, distortion
factor less than 1%, no DC component, no external current
carrying conductor, test sample centered.)
Load impedance > 1MΩ.
Frequency Range: 40 to 10kHz
Limit Operating Conditions:
200A permanently to 1kHz
Derating above 3kHz: 200 A x (1/0.333 F), F in kHz