Emc And Environmental Type Tests - Siemens RUGGEDCOM RSG2300 Installation Manual

Table of Contents

Advertisement

Chapter 6
Certification
Section 6.3

EMC and Environmental Type Tests

The RUGGEDCOM RSG2300 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
40
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and
Interrupts (DC
Power Ports)
Voltage Dips and
Interrupts (A. C.
Power Ports)
Damped Oscillatory
Mains Frequency Voltage
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
+/- 4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
a
Earth Ground Ports
Signal Ports
+/- 4 kV Line-to-Ground,
+/- 2 kV Line-to-Line
DC Power Ports
+/- 2 kV Line-to-Ground,
+/- 1 kV Line-to-Line
AC Power Ports
+/- 4 kV Line-to-Ground,
+/- 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
a
Earth Ground Ports
Enclosure Ports
40 A/m, Continuous,
DC Power Ports
AC Power Ports
60% for 50 periods
AC Power Ports
100% for 5 periods
100% for 50 periods
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
Test Levels
Severity Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV
10 V
1000 A/m for 1 s
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
30% for 1 period
2.5 kV Common,
1 kV Differential
Mode @1 MHz
30 V Continuous,
300 V for 1s
EMC and Environmental Type Tests
RUGGEDCOM RSG2300
Installation Guide
4
4
4
3
4
3
3
4

Advertisement

Table of Contents
loading

Table of Contents