INSTALLATION MANUAL
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODEL: AHV8*UH
(Two Stage Variable Speed Upflow / Horizontal / Low NOx)
57 - 120 MBH INPUT
(16.7 - 35.2 KW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Typical Suspended Furnace / Crawl Space Installation . . . . . . . . . . . . 7
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Upflow Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Horizontal Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Thermostat Chart - AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Thermostat Chart - HP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination 10 ft. (3.0 m) or less . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination more than 10 ft. (3.0 m) . . . . . . . . . . . . . . . . . . . . . 14
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 5
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . . . 9
Nominal Manifold Pressure - Low Fire . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Roof Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
LIST OF SECTIONS
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .20
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
LIST OF FIGURES
Typical Sidewall Vent Application . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Combustion Airflow Path Through The Furnace . . . . . . . . . . . . . . . . .17
Alternate Air Intake, Air Outlet and Chimney Connections . . . . . . . . .17
Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . . . . . . . . . . .17
Typical Chimney Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Horizontal Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . .18
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .18
Pressure Switch Tubing Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
LIST OF TABLES
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . .18
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Field Installed Accessories - Non Electrical . . . . . . . . . . . . . . . . . . . .27
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
271001-UIM-A-0407

Advertisement

Table of Contents
loading

Summary of Contents for Unitary products group AHV8 UH

  • Page 1: Table Of Contents

    INSTALLATION MANUAL HIGH EFFICIENCY EFFICIENCY RATING CERTIFIED TUBULAR HEAT EXCHANGER SERIES MODEL: AHV8*UH ISO 9001 Certified Quality (Two Stage Variable Speed Upflow / Horizontal / Low NOx) Management System 57 - 120 MBH INPUT (16.7 - 35.2 KW) INPUT LIST OF SECTIONS SAFETY .
  • Page 2: Safety

    When outdoor air is used for combustion, the combustion air intake duct of standard ANSI Z21-47 • CSA 2.3. system termination must be located external to the building and in an area where there will be no exposure to the substances listed above. Unitary Products Group...
  • Page 3 248 CMR 5.08(2)(a)1 through 4. Unitary Products Group...
  • Page 4: Ductwork

    In this example, the duct system attached to the plenum has a sufficient area so that the furnace operates at the specified external static pres- sure and within the air temperature rise specified on the nameplate, providing the return duct is properly sized as well. Unitary Products Group...
  • Page 5: Round Duct Size

    To properly design the ductwork for the build- ing, refer to the ASHRAE Fundamentals Handbook, Chapter on “DUCT DESIGN” or a company that specializes in Residential and Modular Home duct designs. Unitary Products Group...
  • Page 6 Lay the furnace on its back. IMPORTANT: This furnace may be installed in a horizontal position on Remove the screws from the toe plate. either side as shown above. It must not be installed on its back. Remove the toe plate. Unitary Products Group...
  • Page 7: Gas Piping

    “INSTALLATION IN FREEZING TEMPERATURES” in Section I IMPORTANT: if an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size. Unitary Products Group...
  • Page 8: Filters

    300 feet per minute (91 m/min). All velocities over this require the use of high velocity filters. Refer to Table 15. GROUNDED JOINT UNION All installations must have a filter installed. DRIP MAY BE INSTALLED INSIDE OR OUTSIDE UNIT. FIGURE 6: Upflow Gas Piping Unitary Products Group...
  • Page 9: Gas Valve

    0.42 0.42 0.42 31.7 0.42 0.42 0.42 33.5 0.42 0.42 0.42 35.4 0.42 0.42 0.38 1000 37.3 0.41 0.37 0.34 1050 39.1 0.37 0.34 0.31 1100 41.0 0.34 0.31 0.28 2500 (LP) 93.2 (LP) 1.03 0.95 0.87 Unitary Products Group...
  • Page 10: Electrical Power

    3. Wire size based on copper conductors, 60º C, 3% voltage drop. "Unit Amps" refers to the full load current. 4. Min wire size (awg) @ 75 ft. one way refers to the minimum recommended field installed wire size. Unitary Products Group...
  • Page 11 (HOT) in the Product Catalog Section. BLK/BLK HUM (HOT) WHT/WHT GRN/GRN EAC (HOT) WIRING INSIDE JUNCTION BOX BURNER JUNCTION COMPARTMENT DOOR SWITCH CLASS 2 SYSTEM CONTROL WIRING BLOWER TO THERMOSTAT COMPARTMENT IGNITION MODULE FIGURE 8: Electrical Wiring Unitary Products Group...
  • Page 12: Thermostat Chart - Ac

    271001-UIM-A-0407 FIGURE 9: Thermostat Chart - AC Unitary Products Group...
  • Page 13: Thermostat Chart - Hp

    271001-UIM-A-0407 FIGURE 10: Thermostat Chart - HP Unitary Products Group...
  • Page 14: Accessory Connections

    2 FT (0.6 m) MIN. 3 FT (0.9 m) RIDGE MIN. FIGURE 12: Vent Termination MORE THAN 10 FT (3.0 m) FROM RIDGE, WALL, OR PARAPET CHIMNEY FIGURE 14: Vent Termination more than 10 ft. (3.0 m) Unitary Products Group...
  • Page 15: Typical Sidewall Vent Application

    ACCESS WALL PANEL FIGURE 16: Typical Sidewall Vent and Termination Configuration VENT CLEARANCES IMPORTANT: The vent must be installed with the following minimum clearances as shown in Figure 17, and must comply with local codes and requirements. Unitary Products Group...
  • Page 16: Home Layout

    Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer. Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent. Unitary Products Group...
  • Page 17 A confined space is an area with less than 50 cu.ft (1.42 m ) per 1,000 Btu/hr (0.2928 kW) input rating for all of the appliances installed in that area. The following must be considered to obtain proper air for combus- tion and ventilation in confined spaces. Unitary Products Group...
  • Page 18 4. The blocking effects of louvers, grilles and screens must be given INLET AIR (b) consideration in calculating free area. If the free area of a specific AIR (a) louver aor grille is not known. FIGURE 23: Outside and Ambient Combustion Air Unitary Products Group...
  • Page 19 Do not rely upon the interlock switch as a main power dis- connect. Blower and burner must never be operated without the blower panel in place. FIGURE 24: Pressure Switch Tubing Routing Unitary Products Group...
  • Page 20 Calculate the furnace input by using one of the following equa- (10.0 cm) in length, a 1/8” (0.3 cm) tee and a 1/8” (0.3 cm) adapter tions. to connect the U-tube manometer or the digital pressure measur- ing equipment to the gas valve pressure ports. Unitary Products Group...
  • Page 21 If the actual input is significantly higher than the furnace input specified on the rating plate then replace the gas orifices with the gas orifices of the proper size for the type of gas you are using. Unitary Products Group...
  • Page 22: Gas Valve

    If adjustment is necessary, set to the following ASSEMBLY PRESSURE specifications. After adjustment, check for gas leakage. U-TUBE SHOWN MANOMETER Refer to Figure 25 for location of pressure regulator adjustment cap and adjustment screws on main gas valve. FIGURE 26: Reading Gas Pressure Unitary Products Group...
  • Page 23: Furnace Control Board

    15 seconds to ramp from one speed to where the humidity is frequently very high during cooling season, such another. as in the southern part of the country. On a call for cooling, the blower Unitary Products Group...
  • Page 24 The control confirms Low flame signal control lockout point is these contacts are open at the beginning of each heat cycle. This would 0.1 microamps DC (µa) indicate a faulty pressure switch or miswiring. Unitary Products Group...
  • Page 25: Filter Performance - Pressure Drop Inches W.c. And (Kpa)

    1501 - 1750 42.49 - 49.55 2452 0.15 0.03736 0.14 0.03487 0.30 0.07473 1751 - 2000 49.56 - 56.63 2542 0.19 0.04733 0.18 0.04484 0.30 0.07473 2001 & Above 56.64 - Above 2987 0.19 0.04733 0.18 0.04484 0.30 0.07473 Unitary Products Group...
  • Page 26: Air Flow Data

    NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details. * The ADJ “D” tap should not be used. Unitary Products Group...
  • Page 27: Field Installed Accessories - Non Electrical

    1BR0221 BOTTOM RETURN FILTER KIT 1-4” FILTER 21” CABINETS 1BR0124 BOTTOM RETURN FILTER KIT 1” FILTER 24-1/2” CABINETS 1BR0224 BOTTOM RETURN FILTER KIT 1-4” FILTER 24-1/2” CABINETS 1HF0801 INTERNAL FILTER KIT WITH 1” FIBER FILTER ALL MODELS Unitary Products Group...
  • Page 28: Wiring Diagram

    SECTION IX: WIRING DIAGRAM FIGURE 28: Wiring Diagram Subject to change without notice. Printed in U.S.A. 271001-UIM-A-0407 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 167187-UIM-C-0806 Unitary 5005 Norman Product York Group Drive 73069...