CONTROL
DESCRIPTION
OneTouch
Basic
Standard
Basic Control:
Allows the user to manually set fan speed to low or high as required to maximize comfort.
Standard Control:
Offers automatic dehumidistat control and the option to select continuous or intermittent fan operation. Setting the wall control to low will
activate the continuous mode.
OneTouch Control:
Allows control of ventilator with the touch of a button. This control will operate as a main wall control. The OneTouch will operate the unit
in Intermittent Mode (20 minutes per hour), continuous low speed, continuous high speed, and off.
All models offer a non- -electric defrost cycle feature which prevents frost and ice buildup within the heat recovery core. When the outside air
temperature falls below 23_F (- -5_C) it is electronically sensed and the dampers close the outside air ports. This allows warm indoor air to
recirculate within the heat recovery core. The frequency of this cycle increases as the outside air temperature decreases.
MODEL
DEFROST*
ERVBBLHA
6 Minutes
HRVBBLHA
6 Minutes
*
All defrost times are in the standard mode (as shipped)
{ Time between defrost when within specified temperature range

CONTROL FEATURES

FAN SPEED
DEHUMIDISTAT
CONTROL
CONTROL
Yes
Yes
Yes
AUTOMATIC DEFROST CYCLE FEATURES
25_F TO 55_F
(---5_C TO ---15_C)
EXCHANGE{
60 Minutes
60 Minutes
CONTINUOUS
MODE
No
Yes
No
Yes
Yes
Yes
4_F TO ---17_F
(---15.6_C TO ---27.3_C)
DEFROST*
EXCHANGE{
6 Minutes
32 Minutes
6 Minutes
32 Minutes
5
INTERMITTENT
MODE
Yes
No
Yes
BELOW ---18_F
(---27.8_C)
DEFROST*
EXCHANGE{
6 Minutes
20 Minutes
6 Minutes
20 Minutes