Crestron CHV-RTS/CHV-RTHS
7. Press fit the sensor into the hole; the clips on either side of the sensor
hold it in place.
Pigtail Wires from Sensor
NOTE: The face of the sensor may be painted or wallpapered to match
the wall. However, keep the small gap around the outer edge clear of any
obstructions.

Hardware Hookup

The sensors are connected to the remote sensor terminals RS1, RS2, and a
common connection RSR on the rear plastic housing of the thermostat.
Separate the thermostat from its backplate. The thermostat terminal blocks
mate to pins protruding out of the front thermostat assembly.
Thermostat firmware release 1.x supports the addition of only two
optional remote sensors (temperature and/or temperature/humidity) per
thermostat on sensor inputs RS1 and RS2.
Thermostat firmware release 2.x supports up to four optional temperature
(CHV-RTS) or slab sensors (CHV-RSS) or two temperature/humidity
sensors (CHV-RTHS).
If you are using one temperature/humidity sensor, then you may add two
temperature sensors (CHV-RTS or CHV-RSS) to the other sensor input.
Installation Guide - DOC. 8189A
Remote Temperature/Humidity Sensors
Mounting Clips
Remote Temperature/Humidity Sensors • 5
Wire Nuts
Wires from Thermostat
1in (2.54cm) Hole