Tyco Fire Product ESFR-22 Instruction Manual

Tyco Fire Product ESFR-22 Instruction Manual

22.4 k-factor pendent sprinklers early suppression, fast response

Advertisement

Quick Links

Model ESFR-22
22.4 K-factor Pendent Sprinklers
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-22 Pendent Sprin-
klers are Early Suppression, Fast
Response Sprinklers having a nominal
K-factor of 22.4 (Ref. to Figure 1). They
are suppression-mode sprinklers that
are especially advantageous as a
means of eliminating the use of in-rack
sprinklers when protecting high-piled
storage.
The Model ESFR-22 Sprinklers are pri-
marily used for ceiling-only sprinkler
protection of (but not limited to) the
following storage applications:
• most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• uncartoned (exposed) expanded
plastics in accordance with NFPA 13
and FM Global standards
• some storage arrangements of
rubber tires, roll paper, flammable
liquids, and aerosols
For more specific criteria, refer to Table
1 as well as the applicable design
standard.
The Model ESFR-22 can protect a
storage arrangement of 40 ft. (12,2 m)
with a ceiling height of 45 ft. (13,7 m)
without requiring in-rack sprinklers.
In addition, it can be installed with a
maximum deflector-to-ceiling distance
of 18 inches (460 mm).
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Applications for the TYCO ESFR Sprin-
klers are expanding beyond currently
recognized installation standards. For
information on research fire tests (e.g.,
with flammable liquids and aerosols)
that may be acceptable to an author-
ity having jurisdiction, contact Tyco Fire
Protection Products (TFPP) Technical
Services.
NOTICE
The Model ESFR-22 Sprinklers described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(NFPA), in addition to the standards of
any authorities having jurisdiction (e.g.,
FM Global). Failure to do so may impair
the performance of these devices.
The owner is responsible for maintaining
their fire protection system and devices
in proper operating condition. Contact
the installing contractor or product
manufacturer with any questions.
In all cases, the appropriate NFPA or FM
installation standard, or other applicable
standard, must be referenced to ensure
applicability and to obtain complete
installation guidelines. The general
guidelines in this technical data sheet
are not intended to provide complete
installation criteria.
Sprinkler
Identification
Number (SIN)
TY8226
DECEMBER 2015
Worldwide
www.tyco-fire.com
Contacts
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
1 inch NPT or
ISO 7-R 1
Discharge Coefficient
K=22.4 gpm/psi
1/2
(320 lpm/bar
Temperature Ratings
165°F (74°C)
205°F (96°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . Stainless Steel
Hook . . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Strut. . . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel
Button
. . . . . . . . . . . . . . Copper, Stainless Steel
Sealing Assembly . . . . . . . . . . . . Nickel w/PTFE
1/2
)
TFP313

Advertisement

loading
Need help?

Need help?

Do you have a question about the ESFR-22 and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Fire Product ESFR-22

  • Page 1 The Model ESFR-22 Sprinklers described storage. herein must be installed and maintained in compliance with this document, as The Model ESFR-22 Sprinklers are pri- well as with the applicable standards of marily used for ceiling-only sprinkler Technical the National Fire Protection Association...
  • Page 2 Compression FLATS Screw - Hook 3-3/16" Strut (81,0 mm) - Link Assembly Button CENTERLINE Sealing OF THERMAL 1-5/8" Assembly SENSING (41,3 mm) ELEMENT 1-3/4" (44,5 mm) DIA. FIGURE 1 MODEL ESFR-22 (TY8226) EARLY SUPPRESSION, FAST RESPONSE PENDENT SPRINKLER 22.4 K-FACTOR...
  • Page 3 PROTECTIVE greater than 30 feet (9,1 m); in some The following general guidelines pro- SPRINKLER cases, installation standards permit vided for the TYCO Model ESFR-22 APPLY WRENCH Pendent Sprinklers can be used for a a greater spacing RECESS TO ESFR-22 quick reference.
  • Page 4 Care and Limited Ordering Maintenance Warranty Procedure TYCO Model ESFR-22 Pendent Sprin- For warranty terms and conditions, visit Contact your local distributor for avail- klers must be maintained and serviced www.tyco-fire.com. ability. When placing an order, indicate in accordance with this section.