Figure 7. Pairing H for Symbio Condenser to Symbio Air Handler Constant two speed
Symbio Air Handler Constant 2 Speed
IMC -
IMC +
COMMON
24VAC IN
T-STAT W2
T-STAT W1
T-STAT Y2
T-STAT Y1
T-STAT G
T-STAT GND
R (24VAC)
COIL DEFROST
O (IN)
OA (OUT)
OB (OUT)
COMMON
MODBUS -
MODBUS +
1 2
J10
AB-J15-2
AB-J15-1
N N o o t t e e : : Electric heat will only operate when using a thermostat. If the condensing unit is a heat pump, electric heat will
not operate in defrost mode.
Thermostat or Sensor Connections
See
J19 or thermostat to J21 on the Symbio 700 in the air handler.
See
Symbio Service and Installation Mobile App to verify that configuration for space controller on
the Symbio 700 matches the desired zone sensor or thermostat application.
20
CONTROL WIRE
J4
J5
UC-J21-5
UC-J21-3
AB-J7-1
AB-J18-1
UC-J16-2
J6
J7
"Thermostat and Zone Sensor Wiring," p. 9
"Symbio Service and Installation Mobile Application," p. 31