h e a t i n g
s y s t e m s
NESTA CHROME 150
Conversion of the appliance from one
î
gas type to another can only be per-
formed by a qualified professional.
Gas conversion shall be performed
î
according to applicable local reg-
ulations. It is prohibited in some
countries. Perform conversion ac-
cording to the gas category spec-
ified for your country on the appli-
ance data plate.
If the boiler is intended to be used
î
with liquefied gas (propane), in-
stalling the boiler below ground
level can be hazardous and prohib-
ited in some countries. Please refer
to applicable local regulations for
installation requirements.
If the boiler is already installed before
î
conversion, the boiler must be turned
off, the power supply must be dis-
connected through the external fuse
or circuit breaker, and the gas supply
to the gas valve must be closed.
Summary
This procedure consists in replacing the fac-
tory-installed
air-gas
ral gas attached to the fan, by an air-gas
mixer
for
G31
liquefied
See Fig. 1 opposite for air-gas mixer location.
See table below for air-gas mixer top and bottom
injector sizes:
Model
N 150 WH
mixer
for
G20
natu-
gas
(Propane).
G31
Top - Bottom
5.3 - 5.0
Gas Conversion Procedure
Make sure that the gas type and pres-
î
sure of the distribution network are com-
patible with the appliance, as per the
information on the appliance data plate.
If the boiler was running before conversion,
î
allow it to cool down before carrying out any
task.
After gas conversion is performed,
i
control the gas pressure and consump-
tion at appliance start up, and perform
the adjustment procedures provided in
3 and
on page 4.
Air-gas mixer (Venturi)
Fig. 1. Air-Gas Mixer Location
EN
Need help?
Do you have a question about the NESTA CHROME 150 and is the answer not in the manual?
Questions and answers