Operation Manual of PROFINET 300 Series

1 Product Overview

Thank you for using VEICHI AC300 series frequency inverter (AC300 and AC310 frequency
inverter) and choosing AC300 PROFINET expansion card AC300PN1. The AC300PN1card is
composed of two boards, AC300PN_CJ、AC300PN_CN, which are connected by communication
line. The physical diagram of the two boards is shown in Figure 1.1

2 Hardware layout and RJ45 interface

2.1 Hardware Layout
The hardware layout of AC300PN1 card is shown in Figure 2.1
The communication status of AC300PN1 card can be displayed by indicator light. The meaning of
different status of each indicator is shown in Table 2.1
Indicator
Indicator
light
status
Light on
Power
Light off
Led1
Light on
Expansion Card
Figure 1.1 Hardware object diagram
Figure 2.1 Hardware layout
Table 2.1 description of indicator light
State description
The power supply is normal
Abnormal power supply
RJ45 port is not started, and
the power system is faulty
1
Processing method
Nothing
Power on or replace the expansion card
Check whether the network cable is connected
correctly, and check whether the GSD version

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 300 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Veichi 300 Series

  • Page 1 Operation Manual of PROFINET 300 Series Expansion Card 1 Product Overview Thank you for using VEICHI AC300 series frequency inverter (AC300 and AC310 frequency inverter) and choosing AC300 PROFINET expansion card AC300PN1. The AC300PN1card is composed of two boards, AC300PN_CJ、AC300PN_CN, which are connected by communication line.
  • Page 2 or configuration is wrong RJ45 port is started, and the Light off Nothing power system is normal Check the frequency inverter fault type, and Flashing Inverter fault then do further processing Led2 The frequency inverter is Light off Nothing normal Check the version of frequency inverter PN Abnormal communication card and software;...
  • Page 3 3 Communication Configuration Description AC300PN1 card supports AC300 series frequency inverters (AC300 and AC310 frequency inverters). The relevant function codes should be set for the AC 300PN1 card to communicate with the frequency inverter normally 3.1 AC300 Communication Configuration 3.1.1 Description of AC300 Inverter Communication Configuration Table 3.1.1 AC300 function code setting Function Setting...
  • Page 4 selection of forward F07.12 is set to 6 rotation in torque 1: Reservation control … 6: RS485 given * F07.12 7: Purchase card * F12.07 0: Set by function code F07.13 Torque control 1: Reservation If restricted by AC300PN1 card, it F07.11 reverse speed limit …...
  • Page 5 Communication given PID feedback 0x3009 Unit 0.1% value Voltage setting of voltage frequency 0x300A Unit 0.1% separation 0x300B Tension setting 0 ~ maximum tension 0x300C Coil diameter setting 0 ~ maximum coil diameter 0x300D Linear speed setting 0 ~ maximum linear speed 0x300E retain 0x300F...
  • Page 6 (address corresponding function is invalid) External borrowing inverter Bit0: y terminal status output terminal Bit1: relay status 0x3018 (address corresponding Bit2: extended Y1 status function is invalid) Bit3: extended relay status AO1 output (address the analog output of external borrowing 0x3019 corresponding function is frequency converter is 0-10000...
  • Page 7 Rated current of frequency C00.27(0x211B) A(0.1A) inverter C00.28(0x211C) Software version C00.29(0x211D) PG feedback frequency 0.01Hz C00.30(0x211E) Timer timing time Second, minute, hour C00.31(0x211F) PID output value 0.1%(0.01%) Sub version of inverter C00.32(0x2120) software C00.33(0x2121) Encoder feedback angle 0.1° C00.34(0x2122) Accumulated error of Z pulse C00.35(0x2123) Z pulse count 0 ~ 63 fault number, 64 ~ 128 warning...
  • Page 8 Select the given source of frequency inverter upper limit 0: Upper limit frequency given Upper limit 1: Reservation If you use AC300PN1 frequency 2: Voltage analog VS given card to limit the upper F01.11 source 3: Current or voltage analog AI given limit frequency, you need selection 4: Current analog AS given...
  • Page 9 (when PLC is disconnected from equipment or PLC is in stop state, Ebus3/A. buS is reported) Processing Processing mode method of selection in case of Ones place: EX-A breaking treatment communication communication failure Tens place: EX-B breaking treatment disconnection between AC300PN1 card F12.50 0: No detection of expansion...
  • Page 10 0x310C Coil diameter setting 0 ~ maximum coil diameter 0x310D Linear speed setting 0 ~ maximum linear speed 0x310E Acceleration time 1 Set unit by function code F01.21 0x310F Deceleration time 1 Set unit by function code F01.21 0 ~ 4000 (corresponding to 0.0% ~ 0x3111 Torque current component 400.0%)
  • Page 11 AO2 output (address corresponding 0x301A 0 ~ 10000 function is invalid) C00.00(0x2100) Given frequency 0.01Hz C00.01(0x2101) Output frequency 0.01Hz C00.02(0x2102) Output current 0.1A C00.03(0x2103) Input voltage 0.1V C00.04(0x2104) Output voltage 0.1V C00.05(0x2105) Mechanical speed 1rpm C00.06(0x2106) Given torque 0.1% C00.07(0x2107) Output torque 0.1% C00.08(0x2108)
  • Page 12 Accumulated power consumption C00.38(0x2126) 10000 KWh (high level) C00.39(0x2127) Power factor angle 1°, 0.1° 3.3 Description of Communication Configuration between AC300PN1 Card and PROFINET Master Station After the communication between the main station and the main station is set up correctly, the communication between the main station and the main station can be realized by setting the communication card with the main station.
  • Page 13 PROFINET mater  station Network switch 1 AC300PN1 slave  AC300PN1 slave  station1 station 2 CN2 CN1 CN2 CN1 Network switch 2 Network switch 3 AC300PN1 slave  AC300PN1  slave  AC300PN1  slave  AC300PN1  slave  station 3 station 4 station 5 station 6 CN2 CN1 CN2 CN1 CN2 CN1 CN2 CN1 Figure 3.3. Schematic diagram of connection tree 3.3.2 communication description AC300PN1 card requires customers to select different PZD lengths for transmission according to different requirements.
  • Page 14 0 ~ 6 monitoring parameters are read periodically Frequency inverter command and frequency setting 8 ~ 0 cycle write function Standard telegram 5 PZD-10/10 Operation status and frequency feedback of frequency inverter 0 ~ 8 monitoring parameters are read periodically Frequency inverter command and frequency setting 0 ~ 10 function parameters are written periodically Standard telegram 6...
  • Page 15 Bit4 0: no fault, 1: fault Bit5 0: GPRS unlock, 1: GPRS lock status Bit6 0: no warning, 1: warning PZD2 Frequency feedback of frequency inverter, unit: 0.01Hz PZD3~PZD12 It can be configured for different monitoring parameters (C00.xx group and part of 0x300 group address) to read data periodically from frequency inverter...
  • Page 16 4 S7-1200 Configuration AC300PN1 Card Example The following shows that S7-1200 is used with V15 to show how to configure with AC310 and AC300PN1 card. Step 1: Build a new project and add S7-1200 master station Open the software and click create new project. Click to configure the device...
  • Page 17 Click add equipment, select the corresponding model of PLC, and click Add. Fill in the project information, project name, path, etc. When finished, click to create.
  • Page 18 Step 2: import the GSDML file In "options", click "manage general station description file" In the pop-up dialog box, first select the path where the GSDML file is stored (be careful not to put the GSDML file in the Chinese path, otherwise an error may be reported), and then select and click Install.
  • Page 19 If the installation is successful, you will be prompted as follows. Click "close" Step 3: configure the slave information Double-click devices and networks in the project Find "other field devices" - "PROFINETIO" - "I/O" - "AC310" - "AC310PN" under the "hardware directory"...
  • Page 20 Select the Ethernet port of PLC, switch to "properties" – “Ethernet address”, set IP address and subnet mask, and click "add subnet" Click "unassigned" of AC310PN, and click "PLC_1. PROFINET interface_1" Select the slave station, click "properties" - "Ethernet address", and set the IP address of the slave station.
  • Page 21 Step 4: select the interactive data station Select the slave station, switch to the "device view", expand the "module" in the right directory, and select the periodic interactive data according to the number of parameters to be sent and received. For example, if there are four parameters for the master station to send to the slave station and the master station to read the status of the slave station, select standard message 2 After that, select the message and click "properties"-"module parameters"...
  • Page 22 Step 5: download configurationSave the configuration, set the IP address of the computer and PLC in the same network segment (do not duplicate the IP address of the slave station), compile and click download...
  • Page 23 Step 6: assign device name Select the slave station and click "online" - "assign device name" Click "update list", where the device name should be consistent with the name in "configured PROFINET device" If there are more than one other devices, you can select other devices to assign the name. After receiving the assigned name, the slave station will save the name.
  • Page 24 5 AC300PN1 Card Fault Direct Replacement When the fault of AC300PN1 card cannot be recovered, it can be replaced directly. It is only necessary to set the corresponding settings on the upper computer of PLC when configuration is needed, and there is no need to reconfigure the equipment Replacement conditions: 1.
  • Page 25 distance of the communication network lines between the two cards should not exceed 100 meters. Due to the long wiring, the signal attenuation and anti-interference performance are reduced. It is recommended to use the switching unit network (as shown in Figure 3.2) 3.