Advertisement

Quick Links

Preface
VH-0800END Module Manual
VH-0800END Module
Manual
V1.0
Archive date 2024-04-07
VEICHI Electric Co., Ltd. provides customers with all-round technical support. Please contact the nearest office or
service center, or directly contact the company headquarters.
Suzhou VEICHI Electric Co., Ltd.
All rights reserved. Contents are subject to change without prior notice.
Suzhou VEICHI Electric Co., Ltd.
Address: 3rd Floor, Building ChunSheng, Lingya Industrial Park, No. 1 Road, Tangtou Community, Shiyan Street,
Baoan District, Shenzhen, China
Hotline: 400-600-0303
Website: www.veichi.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VH-0800END and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Veichi VH-0800END

  • Page 1 Manual V1.0 Archive date 2024-04-07 VEICHI Electric Co., Ltd. provides customers with all-round technical support. Please contact the nearest office or service center, or directly contact the company headquarters. Suzhou VEICHI Electric Co., Ltd. All rights reserved. Contents are subject to change without prior notice.
  • Page 2: Additional Materials

    VH-0800END Module Manual Preface  Brief The VH-0800END series digital input expansion module features 8 channels of digital input, supporting both sourcing and sinking input types. It can be used in conjunction with the VH series main modules.  Additional Materials...
  • Page 3: Safety Statement

     Please use the product in an environment that meets the requirements of design specifications, otherwise it may cause failure, abnormal function or component damages, which is not within the scope of product quality assurance.  VEICHI will not take on any legal responsibility for personal safety accidents and property damage caused by unauthorized operation of the product.
  • Page 4: Operation And Maintenance

    Precautions VH-0800END Module Manual  As the PLC is an open type device, install it in a control cabinet (enclosure protection > IP20) with a lock, accessible only to operators trained in electrical equipment with sufficient electrical knowledge.  Avoid metal debris and wire ends falling into the PLC's ventilation openings during installation to prevent fire, malfunction, or misoperation;...
  • Page 5: Product Information

    VH – 08 00 E ND      Product information VH: VEICHI slim series IO module IO input points 08: 8 points IO output points 00: 0 points Module type E: Logic IO expansion module Output type...
  • Page 6 Product Information VH-0800END Module Manual 1.2 Component Interface Definition On (Green) Normal Power/Run Module abnormal (POWER+RUN) indicator Signal indicator Flash (Green) Module ready or stopped Error indicator On (Red) Module error IO signal Left side (00~07) indicators correspond to 8 input channels, lit when input is active...
  • Page 7: Input Specification

    Product Information VH-0800END Module Manual 1.3 Technical Specification 1.3.1 Power Specification Item Specification Terminal input power rated 24VDC (20.4VDC ~ 28.8VDC) voltage Terminal input power rated 2A (typical at 24V) current Bus input power rated voltage 5VDC (4.75VDC ~ 5.25VDC)
  • Page 8: Software Specification

    Product Information VH-0800END Module Manual 1.3.3 Software Specification Item Specification Software input filter time 0.25ms*N (N=0~255), with a common filter parameter for every group of 8 channels. Input port exception detection None and indication Input channel logic level Independent channel enable...
  • Page 9: Mechanical Installation

    Mechanical Installation VH-0800END Module Manual 2 Mechanical Installation 2.1 Installation Dimension 2.1.1 Module Installation dimension information is shown in the following figure, and the unit is millimeter (mm): 14.5 85.4 Ensure at least 10mm of clearance above the product to accommodate the latch's movement.
  • Page 10 Mechanical Installation VH-0800END Module Manual Description: Depress the rail latch to open it, then place the module on the DIN lead rail and press down on the latch to secure it. Install a DIN snap on both the master and modules. When installing the rail snap, hook the bottom of it to the bottom of the rail and then rotate the snap so that the top end of it is hooked to the top end of the rail, and finally tighten the screws to lock the rail snap.
  • Page 11: Electrical Installation

    Electrical Installation VH-0800END Module Manual 3 Electrical Installation 3.1 Cable Selection In the following table, the lug diameter is for reference only, which can be calculated reasonably according to actual use and adjusted separately. Diameter Name GB/mm2 ANSI/AWG Tubular lug 0.75...
  • Page 12 Electrical Installation VH-0800END Module Manual Left Indicator Left Signal Left Terminal Right Terminal Right Signal Right Indicator 3.3 User Terminal Wiring 3.3.1 Input Terminal Wiring...
  • Page 13: Module Programming

    Module Programming VH-0800END Module Manual 4 Module Programming 4.1 VEICHI CODESYS Programming Software 4.1.1 Create a New Project 4.1.2 Add a New Module Right-click it and select "Add Device."...
  • Page 14 Module Programming VH-0800END Module Manual Click the "Add Device."...
  • Page 15: Configure Parameters

    Module Programming VH-0800END Module Manual 4.1.3 Configure Parameters 4.1.4 Automatic Scanning The VH600 allows manual slot configuration or module scanning after installing the right expansion modules. The configuration and sequence of expansion modules must match the physical setup; otherwise, an alarm will warn of a mismatch between configuration and connection.
  • Page 16 Module Programming VH-0800END Module Manual 4.1.6 Set Parameters 4.1.7 Write User Program 4.1.8 Compile, Download, and Run If the compilation is without errors, download and run the program.