3.2.2 Address Description of AC310 Communication Control Group

Table 3.2.2 Address description of AC310 communication control group
Address
Function description
definition
0x3100
Communication given frequency
0x3101
Communication command setting
Communication given upper limit
0x3104
frequency
0x3105
Communication torque setting
Maximum forward frequency limit of
0x3106
torque control
Maximum reverse frequency limit of
0x3107
torque control
Communication given PID setting
0x3108
value
Communication given PID feedback
0x3109
value
voltage setting of voltage frequency
0x310A
separation
0x310B
Tension setting
Ones place: EX-A breaking treatment
Tens place: EX-B breaking treatment
0: No detection
1: Alarm and freely stop
2: Warn and continuously run
Explanation of data significance
0.01 Hz, e.g.: 5000 corresponds to
50Hz
0: No command
1: Forward running
2: Reverse running
3: Forward jog
4: Reverse jog
5: Slow down and stop
6: Freely stop
7: Fault reset
8: Run forbidden command
9: Run allow command
Unit: 0.01Hz
Unit 0.1%
Unit 0.1%
Unit 0.1%
Unit 0.1%
Unit 0.1%
Unit 0.1%
0 ~ maximum tension
9
(when PLC is
disconnected from
equipment or PLC is in
stop state, Ebus3/A. buS
is reported)
Processing mode
selection in case of
communication failure
between AC300PN1 card
-
and frequency inverter,.
(frequency inverter self
detection, reporting
Ebus1/A. buS)
R/W
characteristic
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W