3 Communication Configuration Description
AC300PN1 card supports AC300 series frequency inverters (AC300 and AC310 frequency
inverters). The relevant function codes should be set for the AC 300PN1 card to communicate with
the frequency inverter normally
3.1 AC300 Communication Configuration
3.1.1 Description of AC300 Inverter Communication Configuration
Function
Name
code
Run command
F00.02
selection
Frequency given
F00.03
source channel
Upper limit
F00.10
frequency source
selection
Torque command
F07.01
setting
F07.10
Speed limit
Table 3.1.1 AC300 function code setting
Setting range
0: Keyboard given
1: Terminal setting
2: RS485
3: Purchase card
0: keyboard number given
1: Keyboard analog
potentiometer setting
...
10: Purchase card
Select the given source of
frequency inverter upper
limit
0: Upper limit frequency
given
1: Reserved
2: Current and voltage
analog AI1 given
3: Current and voltage
analog AI2 given
4: Reserved
5: Terminal pulse PUL
setting
6: RS485 communication
given
7: Purchase card
0: Keyboard number
1: Keyboard
potentiometer setting
...
6: RS485 communication
setting
7: Purchase card
0: Set by function code
3
Setting
Meaning
value
2
The command is given by RS485
6
The frequency is given by RS485
If you use AC300PN1 card to limit
-
the upper limit frequency, you
need to set this to 6
If the torque command is given by
-
AC300PN1 card, it is set to 6
-
If restricted by AC300PN1 card, it