Description Of Pzd Interactive Data; Description Of Data Sent By Master Station - Veichi 300 Series Operation Manual

Profinet expansion card
Table of Contents

Advertisement

Standard telegram 5
Standard telegram 6
PZD is the process data. The master station of PZD can send instructions to the frequency inverter
periodically and read the current status of the frequency inverter periodically. Each PZD can select
configuration and select the parameters to be interacted between the master station and the slave
station. PZD1 and PZD2 are fixed configuration and cannot be modified. The configuration of PZD3
~ PZD12 can be changed according to the specific needs of users. The interactive data is shown in
table 3.5
PZD(Master->Slave)
PZD1
Inverter command
PZD(Slave->Master)
PZD1
Inverter status
Master station sends data
PZD1
Inverter control command
0: No command
1: Forward running
2: Reverse running
3: Forward jog
4: Reverse jog
PZD2
Frequency command of frequency inverter, unit: 0.01Hz
PZD3~PZD12
It can be configured with different control parameters (0x3xxx group address) to issue
periodic instructions to the frequency inverter
Sending data from slave station
PZD1
Bit0
Bit1
Bit2
Bit3
0 ~ 6 monitoring parameters are read periodically
Frequency inverter command and frequency setting
8 ~ 0 cycle write function
PZD-10/10
Operation status and frequency feedback of frequency
inverter
0 ~ 8 monitoring parameters are read periodically
Frequency inverter command and frequency setting
0 ~ 10 function parameters are written periodically
PZD-12/12
Operation status and frequency feedback of frequency
inverter
0 ~ 10 monitoring parameters are read periodically
Table 3.4 Description of PZD interactive data
PZD2
Frequency command of frequency
inverter
PZD2
Frequency feedback of frequency
inverter
Table 3.5 Description of data sent by master station
Table 3.6 Description of data sent by slave station
0: Shutdown state, 1: running state
0: non accelerated state, 1: accelerated state
0: non deceleration state, 1: deceleration state
0: forward, 1: reverse
14
PZD3~PZD12
Other frequency inverter function
parameters
PZD3~PZD12
Other monitoring parameters
5: Slow down and stop
6: Freely stop
7: Fault reset
8: Run forbidden command
9: Run allow command