5.6 k-factor “royal flush ii” pendent concealed sprinklers quick & standard response, extended coverage

Advertisement

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series RFII — 5.6 K-factor
"Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Extended Coverage
General
Description
The Series RFII, 5.6 K-Factor, Ex-
tended Coverage, Light Hazard
(ECLH) "Royal Flush II" Concealed
Pendent Sprinklers are decorative, 3
mm bulb type sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. It is the best choice for archi-
tecturally sensitive areas such as hotel
lobbies, office buildings, churches,
and restaurants.
They are intended for use in automatic
sprinkler systems designed in accord-
ance with standard installation rules
(e.g., NFPA 13). The fast response
thermal sensitivity rating of the Series
RFII (TY3532) provides for a quick re-
sponse extended coverage (QREC)
rating up to an 18 ft. x 18 ft. coverage
area.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components above the ceiling.
The separable two-piece design of the
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
klers and pressure testing of the fire
protection system prior to installation
of a suspended ceiling or application
of the finish coating to a fixed ceiling.
They also permit removal of sus-
pended ceiling panels for access to
building service equipment without
having to first shut down the fire pro-
tection system and remove sprinklers.
Also, the separable two-piece design
of the the Sprinkler provides for 1/2
inch (12,7 mm) of vertical adjustment,
to reduce the accuracy to which the
length of fixed pipe drops to the sprin-
klers must be cut.
The Series RFII
Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
Page 1 of 4
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
WARNINGS
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the integ-
rity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Model/Sprinkler
Identification
Numbers
TY3532
Technical
Data
Approvals
UL and C-UL Listed.
(The listings apply only to the service
conditions indicated in the Design Cri-
teria section.)
NYC under MEA 353-01-E.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
1/2
K = 5.6 GPM/psi
(80,6 LPM/bar
FEBRUARY, 2002
Customer Service/Sales:
Tel: (215) 362-0700 / (800) 523-6512
Fax: (215) 362-5385
Temperature Ratings
155F/68C Sprinkler - 135F/57C Plate
200F/93C Sprinkler - 165F/74C Plate
Adjustment
1/2 inch (12,7 mm)
Finishes
Cover Plate: Chrome Plated, Brass
Plated, or White Painted (Custom paint
matches and colors other than white
are available on request.)
Physical Characteristics
Frame . . . . . . . . . . . . Bronze
Support Cup . . Chrome Plated Steel
Guide Pins . . . . . . Stainless Steel
Deflector . . . . . . . . . . . Bronze
Compression Screw . . . . . . Brass
Bulb
. . . . . . . . . . . . . . Glass
Cap . . . . . . . . Bronze or Copper
Sealing Assembly . . . . . . . . . .
. . . . . . Beryllium Nickel w/Teflon*
Cover Plate . . . . . . . . . . Brass
Retainer . . . . . . . . . . . . Brass
Ejection Spring
. . . Stainless Steel
Patents
U.S.A. Patent Number 4,014,388 may
be applicable to the Series RFII
(TY3532) Concealed Pendent Sprin-
klers. Other patents are pending with
regard to other design features.
1/2
)
TFP260
TFP260 (2-8.1)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CENTRAL RFII Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco Fire Product CENTRAL RFII Series

  • Page 1 Customer Service/Sales: Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Series RFII — 5.6 K-factor “Royal Flush II” Pendent Concealed Sprinklers Quick & Standard Response, Extended Coverage the center of the ceiling hole into plas- General ter board, ceiling tiles, etc.
  • Page 2 Page 2 of 4 TFP260 Operation 1/2" NPT SEALING ASSEMBLY When exposed to heat from a fire, the Cover Plate, which is normally sol- FRAME dered to the Retainer at three points, falls away to expose the Sprinkler As- sembly. At this point the Deflector sup- ported by the Guide Pins drops down SUPPORT CUP WITH...
  • Page 3 TFP260 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE SPRINKLER DIAMETER HOLE FITTING DIMENSION C SPRINKLER SUPPORT CUP ASSEMBLY 1/2" (12,7 mm) THREADED ADJUSTMENT FACE OF CEILING, RETAINING RING MOUNTING SURFACE FIGURE 4 DISPOSABLE PROTECTIVE CAP until it bottoms out against the Support Cup.
  • Page 4 Page 4 of 4 TFP260 The owner is responsible for the in- THE FOREGOING WARRANTY IS Care and spection, testing, and maintenance of MADE IN LIEU OF ANY AND ALL their fire protection system and de- OTHER WARRANTIES EXPRESS OR Maintenance vices in compliance with this docu- IMPLIED, INCLUDING WARRANTIES...