Shelf Ground Connection; Specification For The Shelf Ground Connection Cable - Pentair Schroff AdvancedTCA 11596-100 Service Manual

Shelf, 14-slot
Table of Contents

Advertisement

14-Slot AdvancedTCA Shelf
11596-100/-101/-102/-103

3.5 Shelf Ground Connection

Warning!
This Shelf is intended to be grounded. Ensure that the Shelf Ground terminals
are connected to Protective Earth (PE) of the building.
Danger of electrostatic discharge!
Static electricity can harm delicate components inside the Shelf. You must
wear an ESD wrist strap before exchanging any part or electric component!
The Shelf must be properly grounded via the Shelf Ground Terminal.
The location of the Shelf Ground Terminal is shown in Figure 10.
Figure 10: Shelf ground terminal
1
Shelf Ground Terminal
Torque for Nuts M6: 5.1 Nm (45 in.-lb.)

3.5.1 Specification for the Shelf Ground connection cable

Required wire size: AWG6
Required terminals: Use only double lug terminals with 45° angle tongue.
Example for terminal:
PANDUIT part no. LCD6-14AH-L, or Thomas&Betts part no. 54205UF
See catalogs at www.panduit.com and www.tnb.com.
www.a-tca.com / www.schroff.biz
2
PEM A
16
Shelf Installation
12706892
R1.1, July 23, 2008