Potential for Fire, Smoke and Asphyxiation Hazards
Incorrect installation, adjustment, or misuse of this burner could result in death, severe
personal injury, or substantial property damage.
To the Homeowner or Equipment Owner:
Please read and carefully follow all instructions
provided in this manual regarding your
responsibilities in caring for your heating
equipment.
Contact a professional, qualifi ed service agency for
installation, start-up or service work.
Save this manual for future reference.
RESIDENTIAL BURNERS
To the Professional, Qualifi ed Installer or Service Agency:
Please read and carefully follow all instructions provided
in this manual before installing, starting, or servicing this
burner or heating system.
The Installation must be made in accordance with all state
and local codes having jurisdiction.

Advertisement

Table of Contents
loading

Summary of Contents for Beckett SF

  • Page 1 RESIDENTIAL BURNERS Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe personal injury, or substantial property damage. To the Homeowner or Equipment Owner: To the Professional, Qualifi ed Installer or Service Agency: Please read and carefully follow all instructions Please read and carefully follow all instructions provided provided in this manual regarding your...
  • Page 2: Table Of Contents

    Inspect chimney or direct vent system .......... 6 Combustion air supply ..............6 Clearances to burner and appliance ..........7 Your Beckett burner will provide years of Combustion chamber — Burner retrofi tting ........7 effi cient operation if it is professionally Prepare the Burner ............
  • Page 3: General Information

    This manual contains information that applies to both SM and SF burners. These burners may appear to be basically identical, but there are differences in design and performance. Please...
  • Page 4 ATC code: See Table 2 Note 1: Approval agency listed rating for Model SM is 1.25 to 3.00 gph and Model SF is 1.25 to 5.50 gph. However, the fi ring rate range is limited by the specifi c air tube combination being used.
  • Page 5: Inspect/Prepare Installation Site

    SF90FU SF130FU SF160FU 2.5-5.5 F310 None ○ When contacting Beckett for service information SM Burner Only — Please record the burner serial number (and have 1.25-2.00 2-3/4 SM65VW SM90VW SM130VW SM160VW available when calling or writing). You will fi nd the serial number on the silver label located on the left 2.00-3.00...
  • Page 6: Inspect Chimney Or Direct Vent System

    Section: Inspect/Prepare Installation Site Figure 2 - Chimney Design - Above the Roof NOTE: Correct chimney design is Minimum Clearence: 2 FT. shown by dotted lines. Incorrect chimney design, as shown by the solid lines, may result in down-drafts. Inspect chimney or direct vent system Therefore, it is strongly recommended that an approved insulated stainless steel liner be installed.
  • Page 7: Clearances To Burner And Appliance

    If combustion results are not satisfactory Then attach the air tube to the burner chassis using the with the selected spray pattern, try the other four sheet metal screws provided. Refer to Figure 4 for pattern. details. SF/SM Burner Manual...
  • Page 8: Check/Adjust Electrodes

    fi nished. Mounting dimensions Servicing nozzle line assembly When using the Beckett universal adjustable fl ange, Turn off power to burner before proceeding. mount the air tube at a 2° downward pitch unless otherwise specifi ed by the appliance manufacturer.
  • Page 9 Figure 4. Check/Adjust ‘Z’ Dimension for ‘F’ Heads 1-1/8” DIM. 1-1/8” PLUS SHROUD LENGTH head. A Beckett T501 or T650 gauge may also be used. Adjust the ‘Z’ dimension to ○ Slide the nozzle line forward or back until the the required specifi...
  • Page 10: Installing The Oil Tank And Supply System

    Section: Mount the Burner/Connect Oil Supply Figure 5. – Mounting Burner in Appliance Figure 6. – Inside Tank Gravity Feed System If space between burner air tube and opening exceeds 1/2 inch, pack burner opening with ceramic fiber 1/4” refractory. 4”...
  • Page 11: Wire Burner

    Install a generous capacity fi lter inside the building between the fuel tank shutoff valve and the burner, locating both the fi lter and the valve close to the burner for ease of servicing. Filter should be rated for 50 microns or less. SF/SM Burner Manual...
  • Page 12: Burner Controls

    Section: Burner Controls Burner Controls Wiring GeniSys Model 7505 Control Explosion, Fire, Scald, and Burn Hazard All heating appliances must have HIGH Fire or Explosion Hazard LIMIT protection to interrupt electrical power and shutdown the burner if operating Can cause severe injury, death, or property or safety controls fail and cause a runaway damage.
  • Page 13 To reset from Hard Lockout, hold the reset button for 15 seconds until the yellow light turns on. Ignition Carryover: Once fl ame is established, SF/SM Burner Manual...
  • Page 14: Reset Button Operation

    Section: Burner Controls Figure 9a. – Interrupted ignition, valve-on delay only Figure 9b. – Interrupted ignition, valve-on delay and (no motor-off delay) motor-off delay SAFETY AND SAFETY AND OPERATING OPERATING LIMITS LIMITS THERMOSTAT THERMOSTAT IGNITER IGNITER IGNITER IGNITER L2 (IGN) L2 (IGN) MOTOR MOTOR...
  • Page 15 Control System Features Feature Interrupted Limited reset, Valve-on Burner motor off Alarm ignition Limited recycle delay delay Contacts R7184A — — — R7184B — — R7184P Optional SF/SM Burner Manual...
  • Page 16: Wire Burner

    fl ame is operation. The Beckett A/C Ready Kit (part no. 51950U) established when the vent fi tting is closed. provides this function. Wiring instructions are included with ○...
  • Page 17: Startup / Checkout

    Simulate Flame Failure and Ignition Failure by approximately 2.0 to 2.7 percentage points.) Example: Reduce CO from Refer to the steps for “Start up burner/set 13.5% to 11.5% (2.6% to 5.3% O combustion” and have the system call for heat. SF/SM Burner Manual...
  • Page 18: Perform Regular Maintenance

    Section: Perform Regular Maintenance □ Step 4: Recheck smoke level. It should be Zero. Clean the blower wheel, air inlet, air guide, burner housing and static plate of any lint or foreign -This procedure provides a margin of material. reserve air to accommodate variable □...
  • Page 19: Replacement Parts

    Fuel Units SF only 2591U Single-Stage ‘A’ 5685 Base Pedestal Kit 21188U Two-Stage ‘B’ Fuel Units SM only ** Contact your Beckett Representative for part number 2184404U CleanCut 2460 Single-Stage ‘A’ and pricing. 2256 Pump outlet fi tting (not shown)
  • Page 20: Limited Warranty Information

    The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its “Products” from Beckett for resale, or for incorporation into a product for resale (“Customers”), that its equipment is free from defects in material and workmanship. To qualify for warranty benefi ts, products must be installed by a qualifi...