Oil Traps
To ensure proper oil return to the compressor, a P-type oil trap should be installed at the base of each suction riser of
•
four feet or more.
•
The suction trap must be the same size as the suction line.
Additional traps are necessary for long vertical risers. Add a trap for each length of pipe (approximately 20 feet) to
•
insure proper oil return.
Suction lines must slope ¼" per 10 feet toward the compressor.
•
Install a suction line trap at the evaporator outlet if the suction line rises to a point higher than the connection on the
•
evaporator.
Failure to properly install oil traps can prevent sufficient oil return to the compressor resulting in premature compressor
failure.
Drain Lines
•
Evaporator coil drain lines should be pitched a minimum of 1/2" per foot to allow proper drainage and exit the walk-in
as quickly as possible.
•
Insulate and seal the drain line where it passes through the wall.
•
Copper drain line is required.
•
Freezer compartment drain lines must have heat tape wrapped around the copper drain line and must have ¾" thick
insulation tubing.
•
Do not locate drain line P-traps within the freezer space.
•
Do not reduce the drain line size.
•
Locate a drain line P-trap outside of the cooler space.
•
Any outdoor P-traps exposed to low ambient temperatures should be wrapped with a drain line heater (provide 20
watts of heat per foot of drain line at 0°F, 30 watts per foot at -20°F.
•
Freezer/cooler combo boxes can have one common drain line. However, there must be a P-trap located between the
freezer evaporator and the cooler evaporator located inside the cooler compartment.
•
The cooler compartment P-trap should be located between the cooler evaporator and the external drain location.