Minimum compressor superheat of 20°F may override these recommendations on systems with short line runs.
The condensing unit must have the discharge pressure above the equivalent 105°F condensing pressure (reference
refrigerant charging on page 16).
Correct location and full contact of the expansion valve bulb is extremely important for proper system performance.
ArcticFox Thermostat With LDA
•
To view the ArcticFox LDA Service Video, scan the QR code below.
P/N 550005663
Air Defrost Evaporators Electric Defrost Evaporators
CAUTION
CAUTION
CAUTION
P/N 550005664
18