S T A R T C O S E - 3 3 0 H V E N G I N E E R I N G L T D . Copyright 2006 Startco Engineering Ltd. All rights reserved. Publication: SE-330HV-M Document: S95-C330-0H000 Printed in Canada.
4.1.2 Firmware Upgrade ........18 4.2 Network Communications ........18 ISCLAIMER Troubleshooting ........... 19 Specifications are subject to change without notice. Startco Technical Specifications ........20 Engineering Ltd. is not liable for contingent or 6.1 SE-330HV ............. 20 consequential damages, or for expenses sustained as a result 6.2 Sensing Resistors ...........
TRIP LEVEL setting, and if NGR current 1,000 kVA on medium-voltage systems. is less than 5% of the CT rating, the SE-330HV will trip In an alarm-only system or in a tripping system without on resistor fault. If the resistor-fault circuit is tripped and...
12 seconds and ground-fault current is less of NGR current. than 5% of the CT rating, the SE-330HV will trip on Choose an NGR let-through current and a ground-fault resistor fault. If the resistor-fault circuit is tripped and trip level according to the guidelines in Section 1.1.
NGR is changed, or if the sensing resistor is changed. NOTE: DEFAULT SETTINGS SHOWN. : If the SE-330HV is not calibrated and is supplied FIGURE 1. Configuration Switches. from the load side of the breaker (non-fail-safe mode), calibrate within 12 seconds of power-up or it may trip and 2.1.4.1 S...
Fluorescent flags retain their state when supply voltage is removed. When supply voltage is applied with switch A/D-Converter-Error Trip (4 short): S2 set to FAIL-SAFE, the SE-330HV returns to its state An A/D-converter error has occurred. prior to loss of supply voltage. When supply voltage is...
Outline and panel-cutout dimensions for the SE-330HV Electrical Code Section 10-1108 and National Electrical are shown in Fig. 4. To panel mount the SE-330HV, Code Section 250.36(B). It is not required to be 8 AWG insert it through the panel cutout and secure it with four or larger.
FRONT RIGHT SIDE NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25. 3. MOUNTING SCREWS: M6 OR 0.25-20. 4. USE LIQUID-TIGHT GLAND FOR TERMINAL-BLOCK-ENCLOSURE CABLE ENTRY. FIGURE 9. ER-72KV Sensing Resistor Outline. Pub. SE-330HV-M, March 24, 2006.
(2.21) (0.22) (4.33) (0.22) FRONT SIDE NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 OR 8-32. 3. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED. FIGURE 11. EFCT-1 Sensitive Ground-Fault Current Sensor. Pub. SE-330HV-M, March 24, 2006.
SIDE NOTES: MOUNTING FOOT DIMENSIONS IN MILLIMETRES (INCHES). INSTALLATION TOOL PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL ‘A’) MOUNTING SCREWS: M4 OR 8-32. DETAIL ‘A’ FIGURE 12. SE-CS30-70 Sensitive Ground-Fault Current Sensor. Pub. SE-330HV-M, March 24, 2006.
MOUNTING FOOT INSTALLATION DIMENSIONS IN MILLIMETRES (INCHES). TOOL PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL ‘A’) MOUNTING SCREWS: M4 OR 8-32. DETAIL ‘A’ FIGURE 13. EFCT-26 and SE-CS30-26 Sensitive Ground-Fault Current Sensors. Pub. SE-330HV-M, March 24, 2006.
(GPR) from being transferred to remote equipment. NEUTRAL If the G terminals on the sensing resistor and the SE-330HV are connected to an isolated ground, the ER-SERIES SE-330HV will be exposed to the GPR. If the GPR is SENSING STATION RESISTOR TRIP CIRCUIT...
SE-330HV Neutral-Grounding-Resistor Monitor Rev. 0 4. C 4.1.2 F OMMUNICATIONS IRMWARE PGRADE The local ports can be used to upgrade the SE-330HV 4.1 L OCAL OMMUNICATION ORTS firmware. Upgrade procedure: The SE-330HV has two local communications ports; 1) Remove supply voltage.
See Section 9.2 for sensing-resistor tests. Repeat the calibration procedure after the open or shorted condition has been corrected. Remote Trip The SE-330HV was tripped by a signal from network communications. DIAGNOSTIC LED flash code = L-S-S-L…* Press RESET to clear the trip. EEPROM-Error Trip An error was detected in the EEPROM.
Load.......... 500 Ω (maximum with 1-A and 5-A Input: 24-Vdc supply) Continuous ......2 x CT Rating Isolation........120 Vac 1-Second......20 x CT Rating Parameter........NGR Current EFCT Input: Continuous ......10 x CT Rating 1-Second......25 x CT Rating Pub. SE-330HV-M, March 24, 2006.
Shipping Weight ......20 kg (44 lbs Supply: Universal ac/dc Supply ER-35KV: 48-Vdc Supply Maximum Voltage....22,000 Vac Maximum Current ....220 mA Resistance......100 kΩ Thermal........1 minute on, 120 minutes off Shipping Weight....40 kg (88 lbs) Pub. SE-330HV-M, March 24, 2006.
Applying the test voltage to the R and G terminals will OTE: Program for PDA damage the SE-330HV and the ER sensing resistor. The V TRIP LEVEL is the trip voltage at terminal N, not terminal R. * Available at www.startco.ca.
The connection of the current-transformer secondary to the SE-330HV is not polarity sensitive. c) Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current transformer.