Siemens SIPROTEC easy 7SJ45 Manual page 77

Numerical overcurrent protection
Table of Contents

Advertisement

Available languages

Available languages

Manual 7SJ45
Pickup times
Complete device pulse output
Complete device relay output
Tripping times when switching onto a fault
single phase supply (impulse output)
10000
t [ms]
1000
100
10
1
2
3
4
Figure 2-22
Maximum tripping time when switching onto a
fault, device with pulse output
C53000-K1174-C001-7
approx. 32 ms
approx. 38 ms
I [I
]
5
6
7
8
9
10
N
single phase supply (relay output)
1000
t [ms]
100
10
1
2
3
4
Figure 2-23
Maximum tripping time when switching onto a
fault, device with relay output
Figure 2-22 and Figure 2-23 show maximum values for
single-phase supply. Multi-phase supply will result in shorter
times.