SMA Solar Technology AG
6.6.2 Multi-function Relay
The inverter is equipped with a multi-function relay as standard. This can be activated, for instance,
simultaneously with the red error LED beside the display. Other functions are being planned and can
be retrofitted later via a firmware update.
Here you can connect separate loads both in the event of errors and for trouble-free operation.
The following table contains the maximum permissible voltages and currents:
AC
DC
Cable requirements
Position
Description
A
Cable type
B
External diameter
C
Conductor cross-sectional area
D
Stripped insulation
E
Stripping length
The cable type and cable-laying method must be appropriate to the application and location.
Miniature circuit-breaker
If you connect the multifunction relay to the power distribution grid, you must fuse this with an
individual miniature circuit-breaker.
Installation Manual
Voltage
maximum 240 V
maximum 30 V
Current
maximum 1.0 A
maximum 1.0 A
Value
Double insulated
5 mm ... 12 mm
0.08 mm² ... 2.5 mm²
maximum 8 mm
maximum 15 mm
STP8-17TL-IA-IEN112030
Electrical Connection
53