Premax
4.0 Product and system specification
12
4.1 Material data
Weight, kg/m
Water content, cooling, l/m
Water content, heating, l/m
Copper pipes, quality
Pressure class
4.2 Environmental declaration
Please visit www.lindqst.com
Select Documentation Finder
Select "Premax"
Select "Environmental declaration"
4.3 Working and test pressure
Lindab's waterborne products have been manufactured and tested according to
the Pressure Equipment Directive 97/237EC. The products are classified as SEP –
Sound Engineering Practice.
Pressure table
Pressure class
Max. working pressure
Max. recommended dynamic pressure
Max. test pressure
Even though the battery of the chilled beam can withstand a very high static
working pressure, we recommend a much lower dynamic working pressure, to
avoid noise issues from the valves.
4.4 Water quality
The water preparation and maintenance for the chilled beam water circuit should
be handled by a specialist
To prevent corrosion, the water circuit must be airtight
The water system must also be equipped with aerators to remove any build-up air
in the system.
The water should be oxygen free, to prevent corrosion.
The water system must be filled with potable water that complies with the "EC
directive 98/83/EC".
We reserve the right to make changes
Premax
18
1,6
0,25
EN 12735-2 CU-DHP
PN10
PN10
10 bar
0,2 bar
16 bar