4.0 Product and system specification
12
4.1 Material data
Weight, kg/m
Water content, cooling, l/m
Water content, heating, l/m
Copper pipes, quality
Pressure class
4.2 Environmental declaration
–
Please visit www.lindqst.com
•
Select Documentation Finder
•
Select "Premax"
•
Select "Environmental declaration"
4.3 Working and test pressure
–
Lindab's waterborne products have been manufactured and tested according to
the Pressure Equipment Directive 97/237EC. The products are classified as SEP –
Sound Engineering Practice.
–
Pressure table
Pressure class
Max. working pressure
Max. recommended dynamic pressure
Max. test pressure
–
Even though the battery of the chilled beam can withstand a very high static
working pressure, we recommend a much lower dynamic working pressure, to
avoid noise issues from the valves.
4.4 Water quality
–
The water preparation and maintenance for the chilled beam water circuit should
be handled by a specialist
–
To prevent corrosion, the water circuit must be airtight
–
The water system must also be equipped with aerators to remove any build-up air
in the system.
–
The water should be oxygen free, to prevent corrosion.
–
The water system must be filled with potable water that complies with the "EC
directive 98/83/EC".
We reserve the right to make changes
Premax
18
1,6
0,25
EN 12735-2 CU-DHP
PN10
PN10
10 bar
0,2 bar
16 bar