Specifications

Power:
Physical:
Environmental
Operating Range:
Digital Outputs:
Inputs:
Status Indication:
Protection:
Weight:
Overall
Dimensions:
Listed By:
Mounting Hole
Dimensions:
24VAC ± 10%, 50-60Hz, 1.4 VA of standby power consumption
(Single Class II 70VA or 100VA option available)
Printed Circuit Board and plastic stand offs.
-40° to 176°F (-40 °C to 80°C); 10 to 90% relative humidity, non-condensing
All controls are conformal coated for environmental protection.
Three digital outputs relay contacts rated at 10A resistive @ 125 VAC; Two dedicated for
the compressor contactor 24VAC when "ON" and one dedicated for alarm purposes dry
contact Normally Open (NO)
Four (9) inputs. Dedicated inputs for:
2 High Pressure Switches (HPC)
2 Low Pressure Switches (LPC)
2 Freeze Sensors (FREEZE) 10 K @ 77F Thermistor
1 Condensate Overflow Sensor (CON) 230 K +/- 15%
2 Compressor Call (Y) Signals
Visual (LED) status of power and alarms status indication.
Surge and transient protection circuitry.
0.25 lbs. (0.12 Kg).
5 -13/16" (width) by 4 -1/4" (height) by 1-3/4" (recommended panel depth).
147.32 mm (width) by 108 mm (height) by 32mm (recommended panel depth).
UL
Four mounting holes in rectangular pattern with dimensions between them as follows:
5-5/16" (width) by 3-3/4" (height).
135mm (width) by 95 mm (height).