UNIT PROTECTION MODULE HARDWARE OPERATION IMPORTANT: This manual is for UPM board part numbers 8733 800 259. See controller label as shown in figure 1 to verify correct part number. TABLE OF CONTENTS Specifications ........................3 Unit Protection Module (UPM)................... 4 Power Random Start Up ....................
Specifications Power: 24VAC ± 10%, 50-60Hz, 1.4 VA of standby power consumption (Single Class II 70VA or 100VA option available) Physical: Printed Circuit Board and plastic stand offs. Environmental Operating Range: -40° to 176°F (-40 °C to 80°C); 10 to 90% relative humidity, non-condensing All controls are conformal coated for environmental protection.
Unit Protection Module (UPM) The Unit Protection Module (UPM) as shown in figure 1, is a printed circuit board (PCB) that interfaces with the thermostat or the digital direct controller. The main purpose of this device is to protect the compressors by monitoring the different states of switches and sensors, this device provides time delays and protects the unit against freezing of the water and refrigerant heat exchangers as well as condensate overflow when the appropriate sensors are installed.
The anti short cycle delay is 300sec delay Power Random Start Up on break during normal operation. This feature prevents multiple units sharing same electrical circuit or network from NOTE: tarting at the same time. If the board is set to test mode through the “TEST” DIP switch the delay will be 5 seconds.
Page 6
High pressure protection Low pressure protection If the LPC switch is open upon a Y call the the HPC switch is open upon a Y call the UPM will not energize the CC output and UPM will not energize the CC output and therefore the compressor will remain off, the therefore the compressor will remain off, the fault LED will flash two (2) times for the LPC...
The following table is availab le on the UPM board as well and it depicts the switch Ground position and its associated functionality. The UPM controller takes ground reference from the unit chassis which is connected to the controller via the C-GND spade terminal.
drops below 25% of its value. (18 VAC Free ze protection approximately), the unit will enter brownout The defau lt setting for the freeze limit trip is protection mode. The compressor CC ou tput 30°F, however this can e changed to 15°F will be de-energized and the unit will enter by cutting the R42 resistor located on top of...