Dimensions and Weights

Unit Clearances

Figure 1, p. 14
illustrates the minimum operating and
service clearances for either a single or multiple unit
installation. These clearances are the minimum distances
Figure 1.
Typical installation clearances for single and multiple unit applications
Side by Side
Note 2
Notes:
1. For horizontal discharge unit,
this measurement is reduced to
1'6" (457 MM) to minimize duct
extensions.
2. When equipped with economizer
or barometric relief damper, clearance
distance is to be measured from
protruding hood instead of base.
3. Clearance is the same if any unit
is rotated 180°.
4. Addition clearance required when
barometric damper or economizer
is installed.
Note 4
9 1/8"
232 MM
YZC036E Units
14
6'0"
1829 MM
7'0"
2134 MM
3'0"
914 MM
Note 1
Single Unit
12 1/2"
318 MM
necessary to assure adequate serviceability, cataloged
unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may
result in condenser coil starvation, "short-circuiting" of
exhaust and economizer airflows, or recirculation of hot
condenser air.
End to End
Note 2, 3
4'0"
1219 MM
3'0"
914 MM
3'0"
914 MM
12"
16 3/4"
305 MM
426 MM
YZC048F, YZC060E Units
RT-SVX46G-EN