Connections

Output Connections (See Figure 5, Page 7):
See Table 6, Page 15, for correct wires sizes, VFD to motor.
The output of PID2000 Series drives is 220V single phase
power.
The output power terminals (motor wire connections) are
located on the lower right side of the drive and are labeled
R (Red), Y (Yellow), and B (Black). Feed the motor cable
through the 20mm conduit hole on the bottom right side
and into the appropriate terminals. If the wire is large
enough to require a larger conduit hole, remove the 32mm
knockout and use the appropriate conduit connections.
Attach the motor ground wire to the grounding lug, located
to the upper right of the terminal block. Attach the motor
power wires to the terminals as shown in Figure 5. Table 3
lists the required wire color attachment scheme.
Table 3: Motor Wiring Connections
Main/Run Winding
Start/Aux Winding
Common
Pressure Tank Recommendations:
Minimum tank size is 8 litres. Use a pre-charged pressure
tank with the Drive. The tank size must equal at least 20%
of the pump's rated flow in litres per minute (LPM), but
cannot be less than 8 litres capacity. For example, a pump
rated at 30 LPM would require a tank of 8 litres capacity
or larger. A pump rated at 150 LPM would require a
30 litre tank or larger. A larger tank may increase cycling
of the pump.
Input Ground Screw
Green/Yellow
(Ground)
Input Power Connections
Figure 5: Basic Wiring Connections for Startup.
Aust
EUR
USA
Blue
Blue/Grey
Black
White
Black
Red
Red
Brown
Yellow
See Figures 6–9, Page 12, for information
about I/O Connections O1, I1,V+, and V–.
Table 4: Control Pressure Set Point and
Tank Pre-Charge Pressure Values
Pressure Setpoint
(kPa)
200
250
300
350
400 (Default)
450
500
550
600
650
NOTE: Set the pressure tank's pre-charge to 70% of the
Code
system operating pressure. When using an external set
B
point as well as an internal set point, pre-charge the tank
to 70% of the lower set point of the two. Some
R
applications may require a different percentage when
figuring the set point.
Y
Transducer Connections (See Figure 5):
Use the transducer provided with the drive. Install the
transducer downstream of the tank. Install the transducer in
a tee in a straight section of pipe with at least 1 foot of
straight pipe on each side of the tee (that is, all fittings
must be at least one foot away from the transducer).
Feed the transducer cable through the open 12mm conduit
hole on the bottom of the drive enclosure.
Red to AI+
Black to AI–
Cable Shield
Transducer Cable
Connections
Precharge Pressure
(kPa)
140
175
210
245
280
315
350
385
420
455
Output Ground Screw
Cable Shield Lug
Green/Yellow
(Ground)
Submersible Motor: 3-W. 1-Ph.,
follow colors as shown in Table 3.
6184 0310 EX
7