Installation

INSTALLATION
Mounting (See Figure 3)
Mount the drive in an easily accessible area with
temperature maintained between –4°F and 104°F (–20°C to
40°C). The drive may be mounted outdoors.
To mount the drive, mark the location of the top keyhole
on the wall or stud. Drive a screw into the structure and
hang the drive on it. Back out the screw on the bottom of
the front cover and lift the cover off. Mark the locations of
the bottom two mounting holes. Mount the drive with
screws in all three holes.
Be sure that the ventilation holes are not blocked and that
there is enough space around the drive to allow free air
flow (minimum 75mm clearance, top, bottom, and sides).
Once the drive is mounted, you are ready to connect
the wires.
Typical 220-240 Volt
Circuit Breaker
(Double Width)
Figure 3
Table 2: Circuit Breaker and Wire Sizes
Controller
Model No.
PID2000-1123
NOTE: The circuit breaker protects the drive and is chosen independently
of the motor connected to the drive.
5997 0509 EX
Wire Size
C.B. Size
CB to VFD
(Amps)
2
2.5mm
30
Wiring
To allow for ease of wiring, the wiring area is free of
electronics other than the terminals. Conduit holes and
knockouts are located so that the wire can be fed straight
through to the connectors, with minimal bending. The
terminals accept 1.5 to 4.0mm
NOTE: For convenience in wiring, the input and motor
terminals unplug from the box. Pull them down to remove
them for ease of access. See Figure 4.
BE SURE that when you replace them, they are completely
pushed in and seated.
Note: The best practice is to connect all output wires first
and all input wires last.
Figure 4: Pull the input and motor terminals down
to unplug them for ease of wiring.
Minimum 240VAC
Generator
Capacity (kVA)
7.4
2
wire.
6