Wire Sizing Tables - Pentair PENTEK INTELLIDRIVE PID2000-1123 Installation Manual

Hide thumbs Also See for PENTEK INTELLIDRIVE PID2000-1123:
Table of Contents

Advertisement

Troubleshooting / Wiring Size Charts
Warning
Cause
TPM: Service
Motor current has exceeded S F Amps.
Amps
TPM: Speed
Drive internal temperature limit
Reduced
exceeded.
Jam Warning
Debris in pump has locked rotor.
NOTE: No user action is required when a Warning is displayed.
Table 6: AWG Wire Sizing, VFD to 3-Wire, 1-Phase Motor.
NOTE: Information in this Table applies ONLY to Global Series motors. For other motors, refer to motor
manufacturer's specifications for wire sizing.
VFD
Global
Model
Motor
3-Wire, 1 Phase
G43A0010B2 1.0 220/50/1 0.75
PID2000-1123 G43A0015B2 1.5 220/50/1
G43A0020B2 2.0 220/50/1
Volts/
HP
Hz/Ph
kW
1.1
1.5
Drive Operation
Drive goes into TPM and limits the motor
current.
Drive goes into TPM and limits the motor
current until it is within operating
temperature range.
Drive reverses or pulses motor to try to
free it.
Maximum Cable Length in Metres
Amps
1.5 mm
2.0 mm
2
6.4
100
159
9.4
68
108
11.6
55
87
2.5 mm
3.5 mm
2
2
253
305
173
273
140
221
15
4.0 mm
2
2
305
305