Online Connection Kit Installation

Configuring the Online Connection Kit

Ensure the Online Connection Kit is receiving a Private or Static IP address via
DHCP Server. A public IP will not work;
Ensure that the MAC address is properly Whitelisted if it needs to bypass
a login (splash) page to be able to reach the internet. The MAC address is
printed on a white sticker on the bottom of the Online Connection Kit.
If behind a firewall, ports 22,80, and 443 must be open for the Online
Connection Kit.
10

HVAC Controller Installation

Installing the HVAC Controller in an HVAC Unit
Power Off the HVAC unit;
Connect the HVAC Controller to the thermostat terminals on the HVAC unit -
refer to the Wiring Table to determine proper connections.
THE HVAC CONTROLLER ANTENNA MUST BE FACING THE THERMOSTAT AND
MUST NOT BE TOUCHING OR ENCLOSED BY ANY METAL COMPONENTS IN THE
HVAC UNIT.
THE HVAC CONTROLLER MUST BE MOUNTED SO IT CANNOT FALL INTO THE HVAC
UNIT CONDENSATION PAN. WE RECOMMEND USING PLASTIC CABLE TIES, OR 3M
COMMAND TAPE (NOT SUPPLIED).
Terminal
Terminal
AC Only
Letter
Connection
W
Heat
Y
Compressor
O/B
Reverse Valve
C
Common
R
24V
GL
Fan Low
GH
Fan High
Aux
Aux
NOTE: If the HVAC unit has only one (1) fan speed, connect both fan control
wires – Green and Purple – to the fan terminal (G).
AC + HEAT
HP Only
HP + HEAT
X
X
X
X
Optional
11

Hide quick links: