Start-Up Checklist - Carrier 48FP Controls Operation And Troubleshooting

Single-package heating/cooling units with product integrated controls 50/60 hz
Table of Contents

Advertisement

MODEL NO.:
DATE:
I. PRE-START-UP:
VERIFY THAT UNIT IS LEVEL
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
LOOSEN ALL SHIPPING HOLDDOWN BOLTS AND REMOVE SHIPPING BRACKETS PER INSTRUCTIONS
VERIFY THAT COMPRESSOR SUSPENSION SPRINGS HAVE BEEN LOOSENED PER INSTRUCTIONS
VERIFY OPENING OF ECONOMIZER HOOD
VERIFY INSTALLATION OF EXHAUST HOOD
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
VERIFY THAT POWER SUPPLY MATCHES UNIT DATA PLATE
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
CHECK GAS PIPING FOR LEAKS (48 SERIES ONLY)
CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY
SET SCREW IS TIGHT
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
OPEN SUCTION, DISCHARGE, AND LIQUID LINE SERVICE VALVES
CHECK COMPRESSOR OIL LEVEL SIGHT GLASS AND VERIFY PROPER LEVEL
VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR 24 HOURS
CHECK VOLTAGE IMBALANCELINE-TO-LINE VOLTS:
(AB + AC + BC)/3 = AVERAGE VOLTAGE = _______V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = _______V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = _______ %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE
II. PRELIMINARY CHECKLIST ITEMS
CONTROL SETTINGS FOR NON-NETWORKED, FREESTANDING UNIT
UNIT TO BE OPERATED ON VARIABLE AIR VOLUME (VAV) RATHER THAN CONSTANT VOLUME (CV)
CONFIRM THAT SPACE TEMPERATURE SENSOR (T-55) HAS BEEN WIRED CORRECTLY PER
SPACE TEMPERATURE SENSOR (T-55) SECTION ON PAGE 34
CONFIRM THAT TUBING FOR SPACE AND SUPPLY DUCT PRESSURES HAS BEEN INSTALLED
SET ENTHALPY CONTROL SET POINT ON ECONOMIZER
SET SUPPLY FAN AND "CHECK FILTER" STATUS SWITCHES FOR JOB REQUIREMENTS
UNIT OPTION CHECKLIST
PRESENT?
VARIABLE VOLUME POWER EXHAUST
VARIABLE FREQUENCY DRIVE ON SUPPLY FAN (VAV ONLY)
HOT GAS BYPASS
VAV WITH OCCUPIED HEAT
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 534-738
Book 1 1
Tab 1a 1b

START-UP CHECKLIST

SERIAL NO.:
TECHNICIAN:
AB______V
(DETERMINE BEFORE CONFIGURING CONTROLS):
Printed in U.S.A.
Form 48/50F,J-2T
AC______V
BC______V
Pg CL-1
7-99
Replaces: 48/50F,J,N-1T