Appendix C - Ccn Points List - Carrier 48FP Controls Operation And Troubleshooting

Single-package heating/cooling units with product integrated controls 50/60 hz
Table of Contents

Advertisement

CCN
CCN
TABLE NAME
POINT NAME
SPT
SAT
RAT
CLSP
CCAP
HCAP
ECOS
SFS
SF
SF2S
STATUS01
SP
IGV
INV
OAT
ECON
IQMP
BP
EFRF
PED
FLTS
EXTCLK
MM
FR2
FR3
STO
STATUS02
HS1
HS2
HIR
SATRESET
RH
OARH
HUM
HUM
ENTH
OAC
IAQ
STATUS03
EVAC
PRES
PURG
FSD
DTCC
HCV
FRZ
SMZ
STRST
DEMLT
UNCHT
UNCCL
STDBY
OPTST
UNOCC
IAQPG
OPTSP
OCCHT
STATUS04
OCCCL
OCCFO
NTFCL
PRESS
EVACN
SMKPG
FIRES
TIMOV
DAVCL
FFTST
APPENDIX C — CCN Points List
EXPANDED NAME
Space Temperature
Supply Air Temperature
Return Air Temperature
Control Set Point
Cooling Percentage Total Capacity
Heating Percentage Total Capacity
Economizer Active
Supply Fan Status
Supply Fan Relay
2-Speed Fan Relay*
Duct Static Pressure
Inlet Guide Vanes/Inverter*
Inlet Guide Vanes/Inverter†
Outside Air Temperature
Economizer Damper
IAQ Minimum Damper Position†
Building Pressure
Exhaust/Return Fan
Power Exhaust Damper
Filter Status
External Clock Input
Motormaster/Fan Stage 1*
Condenser Fan Stage 2*
Condenser Fan Stage 3*
Space Temperature Reset
Heat Stage 1
Heat Stage 2
Heat Interlock Relay
Supply Air Set Point Reset
Return/Space Humidity
Outside Air Humidity
Humidifier — Proportional
Humiidifier — Discrete
Enthalpy Status
Outside Air CFM
IAQ (CO
)
2
Evacuation
Pressurization
Smoke Purge
Fire Shutdown
Discrete Time Clock Control
Heating Valve
Freezestat Status
Load-Unload Compressor Factor
Space Temperature Reset
Demand Limit
Unoccupied Heating
Unoccupied Cooling
Unit in Standby
Optimal Start
Unoccupied
IAQ Purge
Optimal Stop
Occupied Heating
Occupied Cooling
Occupied Fan Only
Night Time Free Cooling
Pressurization
Evacuation
Smoke Purge
Fire Shutdown
Timed Override
DAV Control
Factory/Field Test
107
READ/WRITE
DISPLAY FORMAT/
PROPERTIES
ENGINEERING UNITS
RO
–10 to +245 F
RO
–10 to +245 F
RO
–10 to +245 F
RO
RO
0 to 100%
RO
0 to 100%
RO
no/yes
RO
on/off
RO
on/off
RO
on/off
RO
0.0 to 5.0 in. wg
RO
0 to 100%
RO
0 to 100%
RO
–40 to +245 F
RO
0 to 100%
RO
0 to 100%
RO
–0.5 to +0.5 in. wg
RO
on/off
RO
0 to 100%
RO
dirty/clean
RW
on/off
RO
on/off
RO
on/off
RO
on/off
RO
RO
on/off
RO
on/off
RO
on/off
RO
RO
0 to 100%
RO
0 to 100%
RO
0 to 100%
RO
on/off
RO
hi/low
RO
0 to 50,000 CFM
RO
0 to 5000 PPM
RW
alarm/norm
RW
alarm/norm
RW
alarm/norm
RW
alarm/norm
RW
on/off
RO
0 to 100%
RO
alarm/norm
RO
0 to 100%
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
RO
no/yes
F
F
F