Installation sequence
-
Push the inlet connector onto the valve block (figure 1)
-
Screw the valve block into the water inlet (figure 2)
-
Insert siphon trap into the outlet (figure 3)
-
Plug in the main connections (4a). The LED flashes.
-
Attach the GLT - adapter to the wall (figure 4b)
-
Secure the control unit onto the valve block (figure 5A)
-
Connect the control unit to the siphon trap (5B), to the solenoid valve (5D) and to the
GLT - unit (5C)
-
Connect the GLT - unit to the building master control system
-
Check multi-function display
-
Turn on the water. Do not darken the room.
-
Install the urinal to cover the daylight sensor (figure 7)
-
Three minutes later there will be a flush of approx. 10 seconds so that the siphon trap is filled
with water
-
After a break of 8 seconds there will be another flush of approx. 2 seconds
-
Check the GLT - unit from the control room
-
The urinal can then be used
Fault
No flush
Flush, low
Flush, constant
Flushing every 60 sec.  Stadium mode
Residual water does
not flow off
Cause
 Water supply interrupted
 Flow limiter blocked*
 Solenoid valve damaged
 Cable connections interrupted
 Power supply interrupted
 Cleaning session
 Flushstop activated by GLT
 Water supply reduced
 Flow limiter blocked*
 Solenoid valve damaged
 Low water pressure
 Solenoid valve damaged
 Siphon trap or drains blocked
Solution
 Open shut-off or preliminary shut
-off device
 Clean*
 Replace valve block
 Establish connections
 Ensure power supply
 Automatically latest after 30
minutes
 Flushstop deactivate by GLT
 Open shut-off or preliminary shut-
off device
 Clean*
 Replace valve block
 Flush volume increase (page 11.1)
 Replace valve block
 Automatic switchover
 Replace or rectify