Functional specification
Normal function:
A flush is activated when the sensor detects a use. The flush volume can be set to 6 different values
(approx. 0.5 / 1 / 1.5 / 2 / 3 / 4 litres). The factory setting is 0.5 litres (4 bar).
6 ,00
5 ,00
4 ,00
3 ,00
2 ,00
1 ,00
0 ,00
1
2
Recommended adjustment:
Pressure (bar)
Setting
1
1,5
1,5 - 3
1,0
=> 3,5
0,5
Stadium mode:
In the event of frequent use the system automatically switches to stadium mode with flushes at set
intervals of 60 seconds. If the flushing system is used earlier than 60 seconds after the last user the
Stadium mode is activated. If the urinal is then not used for one minute after the flushing, the system
returns to normal mode.
Urinal recognition / flush activation:
The system is fitted with a daylight sensor which detects if the urinal is installed or not. Flushing is only
possible if the daylight sensor detects darkness, i.e. a urinal is installed.
Settings:
All settings are made using the two buttons on the membrane keyboard and confirmed by an LED.
Safety function:
The following functions are integrated in the system:
-
the valve closes as soon as the power supply is fitted and the connection to the electronic circuit
installed
-
the valve closes as soon as the power supply is interrupted
-
no flush activation if no urinal is installed, whereby light hits the daylight sensor
Flush volum e depending on the flow pressure
3
4
5
Flow pressure (bar)
6
7
8
Settings
4 l
3 l
2 l
1,5 l
1 l
0 ,5 l
9
1 0