Non-LoadbreakDry-WellCanisterFusereplacementinstruction(Fig.21
B):
1. De-energize transformer from a remote upstream source
2. Disassemble by loosening 4 set screws
3. Attach a hot stick to the fuse holder eye and pull out
4. Draw fuse holderout
5. Replace the fuse and reinsert the fuse with the fuse holder
6. Assemble by tightening 4 set screws
Loadbreak Dry-Well Canister Fuse replacement instruction (Fig. 21 B):
1. Disassemble by loosening 4 set screws
2. Attach a hot stick to the fuse holder eye
3. Draw fuse holder out rapidly to interrupt load "Load Break"
4. Replace the fuse and insert it rapidly " Load Make"
5. Assemble by tightening 4 set screws.