Fusing

6.6
ELECTRIC SHOCK: Can cause severe injury, death, or damage to equipment. Use a hotstick to service a
Bay-O-Netfuse.Donotinstallafusetocompleteanelectricalcircuit ifafault conditionissuspected.
Donotre-energizesuspectedfailedequipment.Afterinstallingfuses,energize transformerfroma
remote upstream source.
WARNING: Never attempt to remove fuses with pressure on the tank. Severe burns and personal
injury may result from hot dielectric fluid.

Bay-O-Net Fuses

The Bay-O-Net fuse (Fig. 20 A) is used in series with an isolation link or current-limiting fuse "ELSP Back-up
Fuse" to achieve over current protection and high current interrupting current rating. The bay-o-net fuses are
field replaceable without needing to open the transformer tank.
No.4 Business Building-2707, China Central Place
Chaoyang District, Beijing-100021, China
北 京 大 林 绿 源 环 保 科 技 有 限 公 司
BEIJING DAELIM GREEN EP TECH CO., LTD.
Fig. 20 A
Email:info@daelim-electric.com