Technical Reference; Dimensions; Environmental Requirements; Ip-Rating - Xylem FLYGT Concertor FPG 411 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

8 Technical Reference

8.1 Dimensions

1. 112 mm (4.4 in)
2. 45 mm (1.8 in)
3. 106 mm (4.2 in)

8.2 Environmental requirements

Parameter
Operating temperature
Storage temperature
Operating humidity
Sunlight exposure
Maximum altitude

8.3 IP-rating

IP20
8.4 Electrical data
Parameter
Supply voltage
Supply voltage tolerance
Current consumption
FPG 411, FPG 412 Installation, Operation, and Maintenance Manual
1
8 Technical Reference
2
24VDC
_
+
DI
RS485
1
2
3
4
GND
A
B
GND
AI
AO
HMI
_
_
+
+
1
2
3
4
5
PWR
ALARM A
DI1
ALARM B
DI2
DI3
PUMP RUN/CLEAN
3
DI4
PUMP COMMS
DO1
RS485
DO2
DO3
DO4
USB
NODE
ADDRESS
ON
MASTER
OFF
SLAVE
Concertor™
FPG 411
DO1
DO2
ETHERNET
NO COM
NO COM
DO3
DO4
PUMP
NO COM
NO COM
T4
T3
GND
Value
-20°C – +65°C (-4°F – 149°F)
-20°C – +70°C (-4°F – 158°F)
Relative humidity, non-condensing: 5 – 95%
UV-resistant
• With UL approval: Maximum 2000 m (6562 ft)
• Without UL approval: 4000 m (13 123 ft)
Value
+ 24 VDC
± 10%
< 700 mA. Typical: 150 mA
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Flygt concertor fpg 412

Table of Contents