Electrical Connections - gefran GQ 15 Series Manual

Single phase solid state relays

Advertisement

Installation notes
The device must be protected by a high speed
fuse (accessory).
Applications with power solid state relays must
also have a switch to isolate the power line.
Protect the solid state relay against overheating
by using a heatsink (accessory).
The heatsink must be sized according to room
temperature and load current (see technical
data).
Heatsink installation procedure:
spread 1 gram of thermoconductive silicone
paste (we recommend DOW CORNING 340)
on the dissipative metal surfaces of the module.
The surfaces must be clean and the thermocon-
ductive paste must not contain any impurities.
As alternative it is also possible to use the slide
SIL-GQ available as accessory.
Alternately tighten the two fastening screws
until reaching a torque of 0.4...0.6 Nm.
Wait 5 minutes for any excess paste to run off.
Alternately tighten the two fastening screws
until reaching a torque of 1.2...1.4 Nm.

ELECTRICAL CONNECTIONS

Connection of 3-phase load and 2-phase control
Heatsink (accessory)
Connection of 3-phase load with closed/open triangle or star
Attention
The contact surface of the heatsink module
may have a maximum planarity error of 0.1 mm
and maximum roughness of 0.02 mm.
The fastening holes on the heatsink must be
threaded and countersunk.
The heatsink must be grounded.
Connection of single-phase load